NG5-NG7-NG9
English
D01474-16
12
TECHNICAL FEATURES
Ta=25°C unless otherwise specified
Mains side
Description
Symbol
Test Condition
Value and/or
Range
Unit
Supply Voltage Three-phase
Vin
-
400 ± 15%
Veff
Frequency
f
-
50 ÷ 60
Hz
Absorbed Maximum Current per phase
Ifmax
P = Pmax
10 (NG5)
14 (NG7)
18 (NG9)
Aeff
*
Inrush Current
-
Vin=400Veff
< 2,35
A
Power Factor
cos
ϕ
P = Pmax
0,72
-
Absorbed Minimum Power
Pinmin End of charge
< 10
W
Absorbed Maximum Power
Pinmax P = Pmax
5 (NG5)
7 (NG7)
9( NG9)
kW
* Maximum value per model. For the effective current absorption please refer to the charger’s identification label.
Battery side
Description
Symbol
Test Condition
Value and/or
Range
Unit
Output current
I
-
See curve
-
Maximum output current
I1
Phase 1
See curve
A
Output current ripple
-
I = I1
< 5%
-
Absorbed current
Ia
Equipment turned off
< 0,5
mA
Output voltage
U
-
See curve
-
Constant output voltage
U1
Phase 2
See curve
V
Thermal compensation of output voltage
dU1/dT Phase 2
-5
mV /
(°C·cell)
Operating range of Temperature Sensor
∆
T
-
from -20 to +50
°C
Output voltage ripple
-
U = U1
< 1%
-
Maximum power supplied
Pmax U = U1, I = I1
4800 (NG5)
6300 (NG7)
7700 (NG9)
W
Output capacity
C
-
Depend on the
model (>0,2)
mF
General
Description
Symbol
Test Condition
Value and/or
Range
Unit
Operating range of temperature
∆
T
-
from -20 to +50
°C
Maximum relative humidity
RH
-
90%
-
Switching frequency
fc
-
20 ± 5%
kHz
Efficiency
η
At each operation condition
> 87%
-
Maximum size
a×b×c
Without connecting cable
550×270×120
mm
Weight
-
Without connecting cable
9
kg
Enclosure class
-
-
IP20
-
Protection and Safety
Description
Symbol
Test Condition
Value and/or Range
Unit
Insulation
-
Mains to Battery side
1250
V
AC
Insulation
-
Mains side to Earth
1250
V
AC
Insulation
-
Battery side to Earth
1250
V
AC
Leakage current (EMC Filter)
IL
Supplied equipment
< 7
mA
Input fuses
F1-F2-
F3
Inside the equipment
20 (NG5)
20 (NG7)
25 (NG9)
A
Output fuse
F5
Inside the equipment
about 1,2
×
I1
A
Minimum output voltage of operation (Battery Detector)
-
Equipment turn on
1,5
V/cell
Maximum output voltage
Um
Phase 3 (IUIa - IUIUo)
See curve
V
Reverse output polarity
-
At the connection to the Battery
Protection provided
by fuse F5
-
Thermal protection of semiconductors (Temperature of
Thermal Alarm)
-
Ta=55°C
100
°C
Safety Requirements (Rules)
-
EN60335-1, EN60335-2-29
-
-
EMC Requirements (Rules)
-
EN55011, EN61000-4-2,
EN61000-4-4
-
-