P/N 03-0210-501-2400-02 • ISS 04NOV22
3 / 22
Testing
To activate an alarm, push the resettable element or turn the
key clockwise (one click). To reset the device, turn the key
anticlockwise (one click). Reset the control panel after testing.
Replacing the resettable element
Replace the resettable element (or add the breakable element)
as follows:
1. Unlock and remove the front cover as described in
2. Push the element up, and then pull it out (see Figure 5).
3. Replace the resettable element (or add the breakable
element, if required).
4. Replace the front cover.
Analogue values
Analogue values for diagnosing and troubleshooting device
status are shown in the table below.
Value
Device Status
88
Normal
148
Alarm
Analogue values for diagnosing and troubleshooting reference
group, polling group, and device type are shown in the table
below.
Reference Group Polling Group
Device Type
Value
197-226 (212)
197-226 (212)
197-226 (212)
Specifications
Electrical
Operating voltage
16 to 20 VDC
Current consumption
Standby
Alarm
250 µA
280 µA
Mechanical and environmental
IP rating [1]
IP67
Backbox cable knockouts
Top/bottom [2]
1 × threaded knockout (MK20)
2 × threaded knockout (MK20)
Wire size
Minimum
Maximum
0.13 mm² (0.40 mm)
3.31 mm² (2.05 mm)
Operating environment
Operating temperature
Storage temperature
Relative humidity
−25 to +72°C
−25 to +72°C
10 to 95% (noncondensing)
Colour
Red
Green
RAL3028
RAL6024
Material
Body
Contacts
ABS, PC, PMMA, POM
Nickel plated H59, tin plated
QSn6.5-0.1, tin plated H65
Weight [3]
267 g
Dimensions [3]
108 × 108 × 69 mm
[1] When used with the supplied cable gland and plugs.
[2] Top/bottom location subject to installation orientation.
[3] Including the backbox, excluding cable gland and plugs.
Regulatory information
This section provides a summary on the declared
performance according to the Construction Products
Regulation (EU) 305/2011 and Delegated Regulations
(EU) 157/2014 and (EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
Conformity
Notified/Approved body
0370
Manufacturer
Carrier Safety System (Hebei) Co. Ltd.,
80 Changjiang East Road, QETDZ,
Qinhuangdao, Hebei, China 066004.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
Year of first CE marking
2022
Declaration of
Performance number [1]
03-0210-360-3083
EN 54 [1]
EN 54-11 Type A (Outdoor Use)
EN 54-17:2005
Product identification [1]
ZP888R
Intended use
See the product Declaration of
Performance
Declared performance
See the product Declaration of
Performance
2012/19/EU (WEEE Directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: recyclethis.info
[1] The Declaration of Performance only covers red manual call points.
Only red manual call points are covered by EN 54-11 and EN 54-17.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.