8. Connection and Configuration Settings.
8.1. Field Wiring.
The loop wiring is accessed through the back plate of the Detector Head (See Fig 4). The small 2-pin connector
on the left is for future use.
8.2. DIP Switch Settings.
There are two sets of DIPswitches.
The top of the beam has a 4-way switch with the following features.
The address settings is set up via the 8 way DIP switch on the lower part of the beam (See Fig 4).
8.3. Typical Loop Wiring.
Fire Panel
Connections
Loop Output
Input to
Next Device
In Line
ZP7BMR-50/100
Connections
Address switches
and type setting.
Diagnostics
Sensitivity setting
SW3 SW4
‘off’ ‘off’ 50%
sensitivity
‘off’ ‘on’ 35%
sensitivity
‘on’ ‘off’ 25%
sensitivity
‘off’ ‘off’ 12%
sensitivity
SW1 and SW2 have
no function