Chapter 3: Configuration and commissioning
ZP2-A Series Installation Manual
59
The Test menu
Use the Test menu to test system features or devices. The following features or
devices can be tested from this menu:
• Zones
• Control panel input activation
• Control panel and loop output activation
• Output group activation
• Device LED activation
• Remote features and devices
• Batteries
Note:
Tests for outputs and output groups (local or remote) continue for as long
as the test screen is visible. There is no automatic timeout for the output
activation test and system information will not be visible on the LCD for the
duration of the test. Operation not related to the activation test continues as
normal in the background.
Testing zones
To test a zone:
1. Select Test from the Main menu.
2. Select Zones.
3. Select the zone to test, and then press the jog dial to start the test. Press the
jog dial again to end the test for the selected zone.
By default you can select and test up to a maximum of four zones to test at
the same time (the maximum number of zones in test is configurable - see
“Zone configuration” on page 102).
4. Press F2 (Exit) to exit the menu.
Repeat the above steps to end the zone test.
When an alarm is activated in a zone in test:
• The zone test is confirmed on the LCD while the alarm is active
• If a zone board is installed and the corresponding zone is included on the
zone board, then the zone alarm LED is flashing or steady (depending on the
source of the alarm)
• Fire routing, fire protection, sounders, and programmable activations are not
activated
• The control panel resets the initiating device after 5 seconds and clears the
alarm (manual call points must first be closed before an automatic reset can
be applied)
• The event is recorded in the event log
Summary of Contents for ZP2-AF2-P
Page 1: ...ZP2 A Series Installation Manual P N 00 3281 501 2003 01 ISS 22NOV22...
Page 50: ...Chapter 2 Installation 44 ZP2 A Series Installation Manual...
Page 140: ...Chapter 3 Configuration and commissioning 134 ZP2 A Series Installation Manual...
Page 168: ...Appendix C Menu maps 162 ZP2 A Series Installation Manual...
Page 172: ...Appendix D Regulatory information 166 ZP2 A Series Installation Manual...
Page 176: ......