6
ZP2-A Series Operation Manual
Front panel controls and indicators
Operational features described in this section are not available to all users. More
information on control panel operation and access restrictions can be found in
the topic “User levels” on page 19.
Common controls and indicators
The table below includes information for the common controls and indicators
available for fire, repeater, and evacuation panels.
Table 5: Common controls and indicators
Control/LED
LED colour Description
Supply LED
Green
Indicates that the system is powered up.
General Test LED
Yellow
Indicates that one or more features or devices are
being tested.
General Disable LED
Yellow
Indicates that one or more features or devices are
disabled.
General Fault LED
Yellow
Indicates a general fault. The fault LED for the
corresponding device or feature also flashes.
Alarm LED
Red
Indicates a fire alarm.
A flashing LED indicates that the alarm was
activated by a detector. A steady LED indicates that
the alarm was activated by a manual call point.
Fire Routing
On/Acknowledged button
and LED
Red
Cancels a previously configured delay as it counts
down and activates fire routing.
A flashing LED indicates that fire routing has been
activated. A steady LED indicates that the fire
routing signal has been acknowledged by the
remote monitoring equipment.
Fire Routing Delay button
and LED
Yellow
Enables or disables a previously configured fire
routing delay. Cancels a delay as it counts down and
activates fire routing.
A steady LED indicates that a delay is configured
and enabled. A flashing LED indicates that a delay is
counting (fire routing is activated when the
configured delay elapses or when the delay is
cancelled).
The countdown for an active (counting) fire routing
delay or extended fire routing delay is also displayed
on the product LCD (see Figure 3 on page 11):
• When a fire routing delay is counting (and has
not been extended), the LCD displays FR in T1:
xxx sec.
• When an extended fire routing delay is counting
(investigation time), the LCD displays FR in T2:
xxx sec.
Fire Routing
Fault/Disabled/Test LED
Yellow
Indicates a fire routing fault, disablement, or test.
A flashing LED indicates a fault. A steady LED