Connecting zones
Figure 3 below shows connections for the default configuration (option 2).
Figure 3: Connecting zones for the default configuration
1. Zones in the extinguishing area
2. Zone for standard (mixed) fire detection
3. Galvanic barrier (for intrinsically safe
conventional detectors / intrinsically safe
mode only)
4. Zone termination (see “Terminating zones”
below)
Line resistance
Line resistance is shown in the following table.
Table 3: Zone line resistance values
Zone type
EN 54-2, BS 7273
EN 54-13
Intrinsically safe
Mixed detection
40 Ω max.
Not supported [1]
Not supported [1]
Automatic detection
55 Ω max.
50
Ω max
50
Ω max
Manual detection
55 Ω max.
50
Ω max
50
Ω max
[1] Mixed zones are not permitted in installations requiring EN 54-13 or intrinsically safe
configurations.
To measure the line resistance:
1. Disconnect all zone devices.
2. Create a short circuit at the end of the zone line.
3. Measure the resistance between the positive and negative lines with a
multimeter.
Terminating zones
Zone termination is required at all times, whether the zone is used or not. The
type of termination depends on the installation, as shown below.
Summary of Contents for ZP1-X3E Series
Page 1: ...ZP1 X3E Series Installation Manual P N 501 419503 1 20 ISS 20JUL21...
Page 86: ...Chapter 4 Maintenance 80 ZP1 X3E Series Installation Manual...
Page 106: ...Appendix A Configuration presets 100 ZP1 X3E Series Installation Manual...
Page 110: ...Appendix B Regulatory information 104 ZP1 X3E Series Installation Manual...
Page 113: ......
Page 114: ......