ZP1-X3 Operation Manual
15
• Disabled fire sounders are indicated by a steady General Disable LED and a
steady yellow Fire Sounders LED.
• Disabled fire routing is indicated by a steady General Disable LED and a
steady yellow Fire Routing LED.
• Disabled expansion boards are indicated by a steady General Disable LED
and a steady Expansion I/O Fault/Disabled.
Disabled actuators are indicated by a steady General Disable LED and a
steady yellow Released LED.
Disabled safety door monitoring is indicated by a steady General Disable LED
and a steady Door Fault/Disabled LED.
Disabled extinguishing agent flow monitoring is indicated by a steady General
Disable LED and a steady yellow Extinguishing Agent Flow LED.
Disabled extinguishing agent pressure monitoring is indicated by a steady
General Disable LED and a steady yellow Low Pressure LED.
Disabled extinguishing released optical warning panels or signs are indicated
by a steady General Disable LED and a steady yellow Optical Panel On LED.
Disabled start, hold, or abort extinguishing manual call points are indicated by
a steady General Disable LED and a steady yellow LED for MCP Start, MCP
Hold, or MCP Abort.
There is no audible indication.
Note:
Some disablements can prevent or disable the extinguishing event. See
“Extinguishing event prevented” on page 12 for more information.
Tests
• Zone tests are indicated by a steady General Test LED and a steady yellow
Zone LED.
• Extinguishing sounder tests are indicated by a steady General Test LED and
a steady yellow Extinguishing Sounders On LED.
• Fire sounder tests are indicated by a steady General Test LED and a steady
yellow Fire Sounders LED.
• Fire routing tests are indicated by a steady General Test LED and a steady
yellow Fire Routing LED.
Actuator tests are indicated by a steady General Test LED and a steady
yellow Released LED.
Extinguishing agent flow monitoring tests are indicated by a steady General
Test LED and a steady yellow Extinguishing Agent Flow LED.
Extinguishing agent pressure monitoring tests are indicated by a steady
General Test LED and a steady yellow Low Pressure LED.
Extinguishing released optical warning panel or sign tests are indicated by a
steady General Test LED and a steady yellow Optical Panel On LED.