ZP1-X3 Operation Manual
7
Item
Control/LED
LED colour Description
15
General Test button
and LED
Yellow
Tests a system feature or device (when pressed
with the corresponding button).
Testing of some devices requires pressing the
button for more than 3 seconds. (See “Testing
other extinguishing devices” on page 24 for
further details.)
A steady General Test LED and the
corresponding feature or device yellow LED
indicates a test.
16
Low Pressure LEDs Yellow
Indicates the pressure status of the extinguishing
agent container.
A flashing LED indicates that the pressure in the
extinguishing agent container is low (the General
Fault LED also flashes).
A flashing yellow LED indicates an open or short
circuit wiring fault. A steady yellow LED indicates
a disablement or test.
17
Extinguishing Agent
Flow LEDs
Red/Yellow Indicates the extinguishing agent flow status.
A steady red LED indicates that the extinguishing
agent was released out of its container and into
the extinguishing area.
A flashing yellow LED indicates an open or short
circuit wiring fault. A steady yellow LED indicates
a disablement or test.
18
Reset button
Yellow
Resets the control panel and clears all current
system events.
A steady LED indicates that the operator level is
active (see “User levels” on page 17) and that the
control panel can be reset.
A flashing LED indicates that the Reset button is
disabled and that the panel cannot be reset. The
Reset button may be disabled for up to 30
minutes.
19
Panel Silence button
and LED
Yellow
Silences the control panel buzzer and
acknowledges all current events.
A steady LED indicates that all current events are
acknowledged.
Summary of Contents for ZP1-X3