P/N 10-5211-501-AZ70-12 • ISS 29JUN16 

 

A70E-2 Conventional Zone Interface Module 
Installation Sheet 

 

Description 

The A70E-2 Conventional Zone Interface Module provides the 
interface between a conventional zone of detectors and an 
addressable loop. The zone of conventional detectors appears 
as a single addressable device on the addressable loop. 

The module includes the following features: 

• 

Red LED to indicate alarm condition 

• 

Yellow LED to indicate fault condition 

• 

DIN rail or surface mounting 

• 

24 V or loop powered 

• 

Built-in head-out operation 

• 

Drives intrinsically safe equipment 

Installation 

The A70E-2 contains no user-serviceable parts and should not 
be disassembled. 

To install the device: 

1.  Verify that all field wiring is free of open circuits, short 

circuits, and ground faults. 

2.  Make wiring connections as shown in Figure 2 and 

Figure 3. 

A P15 or 35 mm DIN rail can be used. See Figure 1 for 
mounting hole dimensions and locations. The mounting 
hole diameters are 4 mm and centres are at 40.5 and 
67.0 mm. 

Figure 1: A70E-2 dimensions 

 

Wiring 

Connect the supplied transient suppression devices 
(transzorbs) as shown in Figure 2. 

 
Figure 2: Transzorb wiring 

 