All UPS will be set in factory based on customer needs. All related settings can be modified by LCD
display menu.
All this adjustments must be done by trained and authorized personal, or contact ZIGOR to receive training
or technical assistance.
3.5
When internal batteries UPS models are not enough for the acquired backup time because higher capacity battery
is required, the use of A type cabinets is necessary. These cabinets are designed to house different type and
quantity of batteries, so that the installation must be done in the final location.
Follow carefully the steps below:
•
Make sure that the UPS is completely switched off and disconnected from the mains supply before
adding the batteries.
•
Check the voltage of each battery.
•
Assemble the battery cabinet(s) in accordance with the instructions included with the cabinet. Remember
to leave a minimum distance of 500mm between a lateral panel of each battery cabin and the obstacles
there may be around the battery cabinet. In this way, assembly and maintenance of the batteries are
easier.
•
Install the breaker in accordance with the instructions included with the battery cabinet and check it is
open.
•
Place and wire the batteries distributed over the cabinet divisions in accordance with the included battery
assemble drawing.
•
Connect the battery cabinet(s) to the corresponding UPS terminals.
WARNING
Before installing battery, make sure that the UPS and breaker are all turned off. Remove all your metallic
adornment such as finger ring, watch, and so on before connecting battery.
Do not cross connect or short circuit battery poles. Red cable connect to battery positive
connect to negative -
Please use the screwdriver with insulating handle. Do not lay the tools or metallic goods on the battery.
PRECAUTION
When using the external battery it is best to use battery cable which matches UPS maximum power.
When connecting load to UPS, first turn off load and then connect the power cable and finally turn on load one-
by-one.
Inductance loads such as motor, fluorescent lamp, and photocopier are strictly prohibited connecting to UPS
to avoid damage.
Plug UPS on the special socket with over-current protection, for safety reasons the power socket used should
be connected with ground wire.
UPS is likely to have output voltage no matter whether the power input cable is plugged in mains input socket.
If you wish UPS have no output, first break off the switch and then cancel the mains.
When connect laser printer, select the capacity of UPS according to the printer start power because the startup
power is higher.