4. Installation guide
Step1 - Measurement point selection
Sensors are generally deployed on flat surfaces with high stiffness on the
equipment, as close as possible to the rotating bearings, such as the drive
end bearings of motors.
Please refer to national and industry standards for the number and location
of measurement points for each equipment model.
Step2 - Surface treatment
The mounting surface should be as flat as possible, if necessary sandpapered
and cleaned with acetone to remove oil and dirt.
The bottom surface of the installation can be coated with a suitable amount
of silicone oil to increase the accuracy of the vibration signal.
Check the grounding of the equipment before installation to ensure safe use.
Step3 - Sensor installation
The sensor supports three types of mounting: magnet, adhesive and M5 bolt,
with the threaded connection mounting being preferred. If the equipment
does not have the conditions for drilling, a transition plate can also be used
to thread the terminal first and then weld the transition plate to the surface
of the equipment.
If magnetic adsorption is used, the terminal can be fixed by applying
quick-drying adhesive on the bottom surface and silicone around the outer
ring to play a sealing and long-term fixing role.
Installation direction: vertical, horizontal and axial are all possible.
Step4 - Sensor online
Ensure that the gateway is powered up and covered by the ZETA network
and add the terminal to the platform.
Press and hold the button on the front of the terminal for 5 seconds, the
device powers up and the blue light flashes to indicate that the terminal is
attempting to register the gateway (the internal battery was powered up