UFR1002IP
12690-0701-00
Seite
45 / 50
www.ziehl.de
15.6 AS4777,2
When changing the program, all parameters are reset.
South Africa
Australia
NRS097
AS4777,2
My
3AC+N
3AC
3AC+N
Data
230 V
400 V
240 V
Main
Sub
Parameter
Pr1.40
Pr1.41
Pr1.42
menu menu
menu
Ver. 00
Ver. 00
Ver. 00
Ma
ins
con
n
e
c
-t
ion
Connection
3AC-N
3AC
3AC-N
Nominal voltage [V]
230,0
400,0
240,0
Coupling device
no
no
no
S
w
it
ch o
n
con
d
it
ion
s
Voltage
Active
no
no
no
U max.
[V]
250,0
435,0
255,0
U min.
[V]
199,0
342,0
185,0
Frequency Active
no
no
no
F max.
[Hz]
50,55
50,55
50,50
F min.
[Hz]
48,00
48,00
48,50
Switch on
delay
Time
[s]
60
60
60
After
alarms
Switch back
triggered triggered
triggered
Short alarm Active
V
o
lt
age
U >>
Alarm active
yes
yes
no
59.S2
Alarm on
[V]
276,0
478,0
264,0
59>S2
Alarm off
[V]
273,0
475,0
259,0
Delay alarm on [s]
0,16
0,16
1,80
Delay alarm off [s]
60
60
60
U >
Alarm active
yes
yes
yes
59.S1
Alarm on
[V]
253,0
438,0
260,0
59>S1
Alarm off
[V]
250,0
435,0
255,0
Delay alarm on [s]
2,00
2,00
1,80
Delay alarm off [s]
60
60
60
UM>
Alarm active
no
no
yes
59-Av
Alarm on
[V]
253,0
438,0
255,0
Alarm off
[V]
250,0
435,0
250,0
Delay alarm on [s]
0,10
0,10
2,00
Delay alarm off [s]
60
60
60
U <
Alarm active
yes
yes
yes
27.S1
Alarm on
[V]
196,0
339,0
180,0
27<S1
Alarm off
[V]
199,0
342,0
185,0
Delay alarm on [s]
10,00
10,00
1,80
Delay alarm off [s]
60
60
60
U <<
Alarm active
yes
yes
no
27.S2
Alarm on
[V]
115,0
199,0
146,0
27<S2
Alarm off
[V]
117,0
201,0
151,0
Delay alarm on [s]
0,20
0,20
1,80
Delay alarm off [s]
60
60
60
Grey values can only be read (not changed) regardless of the code lock/sealing.