10  Connections 

10.1  Connections 

 

Connection 

Function 

A1 and  A2 

Control voltage Us, see technical data 

15 

Common switching contact for slider outputs 

 (GND) 

Current transducer common earth connection STWA1(H) 

I1 … I8 

Inputs for STWA1(H), potential free contacts or current sensor S1 

+U 

Common supply voltage for potential free contacts or S1 current 
sensor 

16, 26, … 86 

8 outputs for closed gate 

18, 28, … 88 

8 outputs for open slider 

95, 96, 98 

Exhaust performance (95-98 = exhaust on) 

 

10.2  Tipps: 

   Response threshold

 

is too high

 (current flow in the wire is too low): 

  reduce the response threshold by potentiometer 

  if the smallest setting option is insufficient, loop the lines through the current transducer 

STWA1(H) several times. 

   Response threshold

 

is too low

 (base load current must be extinguished): 

  increase the response threshold by potentiometer 

  connect a resistor (0.25 W / 200 V) before the corresponding input of STW81V in parallel to the 

current transducer STWA1(H). 

  750 Ω resistor = increase by a factor 2 

  330 Ω resistor = increase by a factor 4 

  Due to large tolerances that must be considered, we recommend that the best values be 

determined by trial and error method. 

 

Length of connecting cables STWA1(H): 

Up to 50 m, but much longer are also possible. 
Shielding may be required when laid parallel to power lines. 

 

 

11  Troubleshooting 

 

Problem 

Cause 

Remedy 

 
 
 
 

 

Relay does not switch 

Supply voltage is not 
connected to terminals 
A1, A2 

Check that the power supply voltage is 
connected and that it corresponds to the 
voltage of the unit indicated on the side 
nameplate. 

No current through current 
transducer 

Check that the current transducer is 
properly connected and that the receiver is 
turned on 

More than 1 conductive wire 
routed through the 
transducer 

Run only one current-carrying wire through 
the transducer. 

Relay does not turn on 

Check the switching threshold on 
potentiometer I1-I8. 

Relay does not switch at 
potential-free contacts 

Incorrectly connected 
contacts 

Potential-free contacts must be 
connected to +U 

 

 

Summary of Contents for STW81V

Page 1: ...Grid and Plant Protection Operating Manual STW81V updated 2022 09 21 Um For more information and help about this product please scan the QR Code or choose the following link STW81V Operating manual Quick guide Datasheet Connection diagram CAD Data Firmwareupdates FAQ Videos about installation and settings Certificates STW81V 12380 0710 00 Page 1 8 www ziehl de Current relay 8 channel single evalua...

Page 2: ... with the following instructions is mandatory to ensure the functionality and safety of the product If the following instructions given especially but not limited for general safety transport storage mounting operating conditions commissioning and disposal recycling are not observed the product may not operate safely and may cause a hazard to the life and limb of users and third parties Deviations...

Page 3: ...nputs Usage The STW81V current relay is particularly suitable for the central control of gate valves in extraction systems to be actuated according to the operating status of individual machines It can simultaneously control the central extraction system 5 Functional overview OR 8 inputs I1 I8 individual evaluation of 8 machines STWA1 H current sensor S1 or contact 8 relays for sliders with open a...

Page 4: ...responding relay activates and the yellow LED goes on If the current on STWA1 H falls below the set switching threshold the corresponding relay is de energized with a fixed delay of 10 seconds If it is the last relay energized it switches off 20 s after K9 At the same time all 8 inputs are OR connected If current is detected in at least one of the monitored circuits relay K9 closes contacts 95 98 ...

Page 5: ...gulations for the installation and operation of electrical systems The devices are built and tested according to DIN VDE EN IEC standards and leave the factory in perfect safety condition To maintain this condition follow the safety instructions in the manual marked Caution Failure to follow the safety instructions could result in death personal injury or property damage to the device itself and t...

Page 6: ...corresponding input of STW81V in parallel to the current transducer STWA1 H 750 Ω resistor increase by a factor 2 330 Ω resistor increase by a factor 4 Due to large tolerances that must be considered we recommend that the best values be determined by trial and error method Length of connecting cables STWA1 H Up to 50 m but much longer are also possible Shielding may be required when laid parallel ...

Page 7: ...action Capacity Utilization category AC 15 Ie 3 A Ue 250 V Nominal operating current Nominal operating voltage DC 13 DC 13 DC 13 Ie 2 A Ie 0 4 A Ie 0 2 A Ue 24 V Ue 120 V Ue 240 V Transducer connection Connectable transducers 1 STWA1 H transducer or potential free contact or 1 S1 current sensor per channel AC internal resistance ca 15kΩ Overload capacity STWA1 H max 100A continuous max 300A for 10...

Page 8: ...torque 8 mm 0 5 Nm Degree of protection Casing terminals IP 30 IP20 Fastening Snap on mounting on 35 mm mounting rail according to EN 60 715 or screw fixing M 4 additional clamp is not included Weight approx 300 kg Subject to technical changes 2 Type V8 Dimensions in mm 1 Upper part cover 2 Bottom part base 3 Snap bar for snap mounting 4 Sealing latch 5 Front panel insert front panel 6 Position do...

Reviews: