MU100W 

12100-0703-00

 

Page

 

3 / 6 

www.ziehl.de 

  

 

Overview of functions 

Applications 

are the creation of adjusting commands or the detection of mechanical elements, e.g. 

flaps. 

 

Connection of a potentiometer 0...500 Ω to 0...10 kΩ 

 

Zero adjustable 0 ... 40 % of Scale 

 

Full-scale adjustable 60 ... 100 % of Scale 

 

Easy adjusting of zero and Full-scale by pressing a button 

 

Analog output 0 ... 20 mA /4 ... 20 mA 

 

Analog output 0 ... 10 V 

 

LEDs for display of operative state 

 

Universal supply AC/DC 24-240 V 

 

Housing for DIN-rail or wall-mount, 35 mm wide, 

 

mounting height 58 mm 

 

Connecting diagram 

See 1 Display and controls 
 

Important Information 

 

 

Attention! 
Hazardous voltage! 
Will cause death or serious injury. Turn off and lock out all power 
supplying this device before working on this device. 

 
 

 

Attention! 
The device has a universal power supply, that is suitable for DC- and AC voltages. 
Before connecting the device to supply- voltage make sure that the 
connected voltage corresponds with the voltage on the lateral type on the device. 

 
 

Observe the maximum temperature permissible when installing in switching cabinet. Make sure 
sufficient space to other equipment or heat sources. If the cooling becomes more difficult e.g. 
through close proximity of apparatus with elevated surface temperature or hindrance of the 
cooling air, the tolerable environmental temperature is diminishing. 

 

To use the equipment flawless and safe, transport and store properly, install and start professionally and 
operate as directed. 
Only let persons work with the equipment who are familiar with installation, start and use and who have 
appropriate qualification corresponding to their function. They must observe the contents of the instructions 
manual, the information which are written on the equipment and the relevant security instructions for the 
setting up and the use of electrical units. 
The equipment is built according to  DIN / EN and checked and leave the plant according to security in 
perfect condition. If, in any case the information in the instructions manual is not sufficient, please contact 
our company or the responsible representative. 
To  maintain  this  condition,  you  must  observe  the  safety  instructions  in  this  instruction  manual  titled 
“Important  Information”.  Failure  to  follow  the  safety  instructions  may  result  in  death,  personal  injury,  or 
property damage to the equipment itself and other equipment and facilities. 
Instead of the industrial norms and regulations written in this instruction manual valid for Europe, you must 
observe out of their geographical scope the valid and relevant regulations of the corresponding country. 

Summary of Contents for MU100W

Page 1: ...iehl de www ziehl de Temperature Relays and MINIKA Mains Monitoring Digital Panelmeters MINIPAN Switching Relays and Controls Measuring Transducers Grid and Plant Protection Operating Manual MU100W updated 2018 11 09 sm MU100W 12100 0703 00 Page 1 6 www ziehl de Measuring Transducer for Potentiometers ...

Page 2: ...7 4 Current voltage output 4 7 5 Factory setting 4 8 Technical data 5 9 Housing Type V2 6 1 Display and controls 2 Application and short description The MU100W measuring transducer converts the position of a potentiometer into a linear signal 0 4 20 mA respectively 0 10 V Zero can be easily scaled 0 40 Full scale 60 100 of the range of the potentiometers by pressing a button The built in universal...

Page 3: ...close proximity of apparatus with elevated surface temperature or hindrance of the cooling air the tolerable environmental temperature is diminishing To use the equipment flawless and safe transport and store properly install and start professionally and operate as directed Only let persons work with the equipment who are familiar with installation start and use and who have appropriate qualificat...

Page 4: ...arameterization mode press the button Zero for 10s when applying the control voltage until the power LED starts to flash To exit parameterization mode prematurely press the Full scale and zero buttons at the same time The parameterization mode is automatically exited after 10 minutes The set values remain stored even when the control voltage is switched off 7 2 Adjustment zero point 0 40 of the ad...

Page 5: ...00 V Overvoltage category II reinforced insulation Pollution degree 2 Rated insulation voltage Ui 250 V On period 100 EMC tests Emission EN 61000 6 3 Immunity EN 61000 6 2 Installation conditions Permissible ambient temperature 20 C 60 C Permissible storage temperature 20 C 70 C Installation height 2000 m over N N Climatic conditions 5 85 rel humidity no condensation Permissible wiring temperature...

Page 6: ...l base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzeichen für unten position downward 7 Riegel bei Wandbefestigung mit Schrauben Riegelbohrung Ø 4 2 mm for fixing to wall with screws Ø 4 2 48 58 45 3 61 8 16 5 90 Option 98 116 35 3 4 1 2 5 7 6 ...

Reviews: