8.7.1
Setting for Rampup time and Rampdown time
By separate menus for Rampup time and Rampdown time an adjustment is possible to individual
system conditions.
This function is switched behind the actual controller function.
Rampup time
Time setting in which the automatic controller output from 0 % to 100 % rises.
Setting range: 0...250 sec.
Factory setting depending on motor
Rampdown time
Time setting in which the automatic controller output from 100 % to 0 % reduces.
Setting range: 0...250 sec.
Factory setting depending on motor
0 .. 100 %
3
4
1
2
09.05.2007
v_hochlaufzeit_ruecklaufzeit.vsd
1
external Signal
2
Setting
3
Rampup time
4
Rampdown time
Assembly instructions
ECblue
Programming by hand held terminal A-G-247NW
L-BAL-F055D-GB 1634 Index 002
Part.-No.
37/51