Control/Manual
(7D)
Switch over
“
automatic control
”
/
“
Speed manual
”
Possible only for operation with one control circuit!
Heating/Cooling
(8D)
Switch over control function (e.g.
“
heating
”
/
“
cooling
”
)
1.Setp+Pband1/2
(15D)
for control circuit 1: Switch over Setpoint 1/2 and Pband 1/1
When programming this function,
“
Setting
”
additionally lists the parameter:
“
1.Pband2
for control circuit 1.
”
Only active in operation with a second control circuit!
E1 / E2
(4D)
The output for the control circuit 2 is placed at the speci
fi
ed motor output, in addition to
“
A1
”
. Control circuit 1 has no output for the duration of the switching.
2. Setpoint 1/2
(9D)
for control circuit 2: Switch over
“
2. Setpoint 1
”
/
“
2. Setpoint 2
”
2.Setp+Pband1/2
(16D)
for control circuit 2: Switch over Setpoint 1/2 and Pband 1/2
When programming this function,
“
Setting
”
additionally lists the parameter:
“
2Pband2
for control circuit 2.
”
9.10.2.2
Enable ON/OFF function
|
1D
|
Remote control (electronic switch-off) and Reset after motor fault by potential-free contact. The power
unit is switched off electronically, the device can still be operated in the off state. Signal inputs and
outputs remain active.
When operating with two control circuits, the switch-off affects both outputs, i.e. the inverter output of
control circuit 1 and the signal output 0 - 10 V of control circuit 2 .
•
A programmed operating indicator relay (factory set
“
K1 function
”
=
|
1K
|
) reports the switch-off.
•
A programmed alarm relay (factory set
“
K2 function
”
=
|
2 K
|
) does not report the switch-off.
Display
STOP
for switch OFF
•
Controller
“
ON
”
for closed contact
(factory setting).
•
Controller
“
OFF
”
with opened contact
When inverting in reverse i.e. equipment
“
OFF
”
with closed contact.
D1
D1
D1
D1
Digital IN 1
Digital IN 1
ON
OFF
10.05.2007
v_1d_freigabe_d1_d1.vsd
Contact at digital input e.g.
“
Digital In 1
”
Attention!
No disconnection (isolation) when turned off, in accordance with VBG4
§
6)!
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003