Setting
Setpoint2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (display as long as no allocation is carried
out:
|
- - - - -
|
IO Setup).
- - - - -
Setpoint2
Setting
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Passive sensor type
“
TF
”
,
“
PT1000
”
Setting range: 0 - 200.0 K (Kelvin)
Factory setting: 5.0 K, (at
2.02
: 20.0 K)
active Sensor type
“
MTG-120V
”
Setting range: -120.0...+120.0 K
Factory setting: 65.0 K
5.0 K
Pband
Setting
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
OFF
Min. Speed
Setting
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
50.0 Hz
Max. Speed
Setting
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
OFF
Manual mode
Setting
Speed Manual mode
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
50.0 Hz
Speed man.
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
36/123