9.5.5
Networking via MODBUS
It is possible to network several devices with each other. The device uses the MODBUS-RTU as the
protocol for the RS-485 interface.
Bus Address
The device address is factory set to the highest available MODBUS address: 247.
Setting range MODBUS Address: 1 - 247.
UART Baudrate
Setting transfer rate
Valid values: 4800, 9600, 19200, 38400, 115200
Factory setting: 19200
UART Mode
Setting transfer format
Valid values: 8N1, 8O1, 8E1, 8N2
Factory setting: 8E1
9.6
Menu group
“
Motor Setup
”
Motor Setup
Rated speed
MotorRatedCurr.
* The following controller presettings are dependent on the
respective motor design and are only shown for information.
•
Rated speed
•
MotorRatedCurr.
•
Rotat. Direction
•
Value motorheating
Rampup time
Rampdown time
Rotat. Direction
Value motorheating
Suppression1
Range1 min.
Range1 max.
Assembly instructions
ECblue BASIC-MODBUS, ECblue BASIC
Hand held terminal A-G-247NW
L-BAL-F079D-GB 2044 Index 002
Part.-No.
57/80