– 10 –
OPERATION DETAILS
DRY MODE OPERATION
•
The compressor will stop when operational frequency reached the minimum frequency and that condition has
been kept for
★
1 seconds and the room temperature becomes 1.3
℃ lower than it
was set.
•
The compressor will re-start when room temperature becomes 0.7
℃
higher than
it
was set.
•
The operational frequency will be set every
★
2 seconds of operation.
The operational frequency setting will be calculated based on the deviation of the room temperature and the
set temperature on one end and the deviation factor at the time of previous setting on another.
Indoor fan
Selected speed
Stop
Super low
3min.
MAX
MAX
0
Hz
Frequency of
compressor
Designated
temperature
Room temperature
★
3
★
3
MIN
★
4
MIN
★
4
Selected speed
-1.3˚C
0.7˚C
★
1
120
180
★
2
40
60
★
3
68.0Hz
72.0Hz
★
4
32.0Hz
32.0Hz
S 1731
S 1735