ZGR VERSATILE RT - 10 KVA
Manual de operaciones
www.zigor.com
21
12
Initialization fault
Beep continuously
Fault LED lit
13
P-Battery Charger fault
Beep continuously
Fault LED lit
14
N-Battery Charger fault
Beep continuously
Fault LED lit
15
DC Bus over voltage
Beep continuously
Fault LED lit
16
DC Bus below voltage
Beep continuously
Fault LED lit
17
DC bus unbalance
Beep continuously
Fault LED lit
18
Soft start failed
Beep continuously
Fault LED lit
19
Rectifier Over Temperature
Twice per second
Fault LED lit
20
Inverter Over temperature
Twice per second
Fault LED lit
21
Input N loss
Twice per second
Fault LED lit
22
Battery reverse
Twice per second
Fault LED lit
23
Cable connection error
Twice per second
Fault LED lit
24
CAN comm. Fault
Twice per second
Fault LED lit
25
Parallel load sharing fault
Twice per second
Fault LED lit
26
Battery over voltage
Once per second
Fault LED blinking
27
Mains volt. reverse (Reserved)
Once per second
Fault LED blinking
28
Bypass reverse (Reserved)
Once per second
Fault LED blinking
29
Output Short-circuit
Once per second
Fault LED blinking
30
Rectifier over current
Once per second
Fault LED blinking
31
Bypass over current
Once per second
BPS LED blinking
32
Overload
Once per second
INV or BPS blinking
33
No battery
Once per second
BATTERY blinking
34
Battery under voltage
Once per second
BATTERY blinking
35
Battery low pre-warning
Once per second
BATTERY blinking
36
Internal Communication Error
Once per second
Bypass LED lit
37
DC component over limit.
Once per 2 seconds
INV blinking
38
Parallel Overload
Once per 2 seconds
INV blinking
39
Mains volt. Abnormal
Once per 2 seconds
BATTERY LED lit
40
Mains freq. abnormal
Once per 2 seconds
BATTERY LED lit
41
Bypass Not Available
BPS blinking
42
Bypass unable to trace
BPS blinking
43
Boot is invalid
Table 3-2 List of possible events of ZGR VERSATILE RT - 10 KVA