ZGR VERSATILE RT - 10 KVA
Manual de operaciones
www.zigor.com
12
restart it.
3.2.4
Output short circuit
When the UPS output is in short circuit, the UPS will cut off the output, fault indictor will be on (red), the LCD will
display output is in short circuit, long beeps come.
If so, please disconnect the load in short circuit, cut off the UPS input power and wait for 10mins, the UPS will
shut down automatically or press the off button to shut down in after10s. Before restarting the UPS, please make
sure that the short circuit problem has been solved.
3.2.5
Battery self-Test
when the UPS has no need of the battery self-
batteries can do the self-test automatically per 30 days. Three kinds of Battery Self-test Time can be chose as
below.
1.
When choosing 10 s, UPS can transfer to Battery Mode automatically per 30 days. And the Battery Self-
test Time is 10 seconds.
2.
When choosing 10 m, UPS can transfer to Battery Mode automatically per 30 days. And the Battery Self-
test Time is 10 minutes.
3.
When choosing EOD UPS can transfer to Battery Mode automatically per 30 days. And the Battery Self-
test Time is EOD.
Turn on/off UPS
3.3.1
Connecting with Utility
•
according to the user s manual.
•
Switch on the UPS
The internal fan of the UPS starts spinning, the UPS is performing self-diagnostics until buzzer beeps twice to
show the UPS is normal. Then, the UPS goes to bypass supply, Utility LED and Bypass LED turn green, the
supplied by the inverter now.
No matter the UPS is operated normally or not, the LCD display will indicate current status. The top lines display
the UPS operational status and the bottom lines indicate alarm conditions when they occur.
PRECAUTION
Make sure grounding is properly done.
PRECAUTION
Check to see if the load is safely connected with the output of the UPS. If the load is not ready to receive power
from the UPS, make sure that it is safely isolated from the UPS output terminals