Installation and operating instructions V00 61
The safety of the grid may be influenced due to the wrong safety setting!
•The default parameters settings comply with the local regulations.
•Don’t change the values of the default safety regulation values unless permitted by the
utility provider!
9.4.12 Safety regulations setting
Enter the sub-menu “Advanced Setting” and press the "
" button to input the
password. The password is required if you want to change some parameters. Please
get the correct password from the service engineer. Enter the correct password and
"
" to enter the advanced setting sub-menu page.
Then select the “Safety Setting” item and press the "
" button then enter the
safety parameters page.
Password
Password:0 0 0 0
0
Overload Setting
Active power control
Reactive power control
PV Mode Setting
Advanced Setting
EEG Setting
Safety Setting
At the safety regulation parameter page, use the "
▲
" or "
▼
" button to modify the
selected parameter and confirm with the "
" button. Then modify the next
parameter in turn. Parameter modification is finished after the Enter key is pressed.
Press the "ESC" button to cancel.
Safety
Standard:
DE VDE-AR-N 4105
OVP2
:
265.5 V
OVP1
:
255.0 V
UVP1
:
185.0 V
UVP2
:
180.0 V
10Min-Mean
:
180.5 V
Safety
OFP2
:
54.50 Hz
OFP1
:
UFP1
:
UFP2
:
53.50 Hz
47.50 Hz
45.50 Hz
There are two pages for safety regulation parameters setup. After modifying the
last parameter of the first page, the page will automatically jump to the second
page.