PRECISION CURRENT SENSE TRANSFORMER 

ELECTRICAL DATA 

FEATURES 

• 

Measuring current transformer acc. IEC 61869-1, IEC 61869-2 

• 

Designed for IEC 61851-1 charging applications 

• 

Ideal for current / power monitoring and metering applications 

• 

Current rating 50 Arms 

• 

Primary to secondary insulation according OVC III / PD 3 

• 

Dielectric strength 4 kV AC 

• 

UL approved class B insulation system 

• 

TÜV type approved 

Primary current 

rating 

overload withstand 

impulse current withstand 

 

50 A 

70 A  (1min.) 

2 kA  (half wave) 

Approved ratings 

primary current 

extended current 

secondary current 

short time thermal current 

system voltage 

(TÜV) 

50 A 

120 % 

50 mA 

1 kA 

≤ 800 V 

Working frequency 

50/60 Hz (sin.) 

Turns ratio N

S

:N

P

 

1000:1 

Accuracy 

classification 

magnitude error 

phase error 

(at R

L

=50Ω) 

Class 0.2 (acc. IEC 61869-2) 

≤ 0.5%  (< 0.1%  typ. @ 0.5 - 50 A) 

≤ 1° 

(< 0.3°   typ. @ 0.5 - 50 A) 

Secondary output

 

transformation ratio 

max. voltage 

burden resistor R

L

 

 

60  mV/A (typ. Ta=23°C, R

L

=50Ω, f=50Hz) 

3.0  V 

50  Ω (recommended) 

Windings 

PRI DC resistance 

SEC DC resistance 

 

< 0.2 mΩ   (typ.) 

≤ 60 Ω  

(< 50 Ω typ.) 

Dielectric strength 

PRI to SEC 

(at sea level, 1mA, 50/60Hz, 1sec.) 

4 kV AC 

Insulation 

PRI to SEC 

(acc. IEC60664-1) 

Reinforced (300 VAC, OVC III, PD 3) 

Isolation spacing 

clearance/creepage 

solid insulation (dti) 

(Primary to Secondary) 

≥ 11.5 mm 

1.0 mm 

Temperature range 

operating / storage 

 
-

40°C (-40°F) to 85°C (185°F) 

Vibration resistance

 

0.062" (1.5 mm) DA at 10–55 Hz 

Shock resistance

 

10 g 

Enclosure 

material group 

flammability 

 

IIIa 

UL94 V-0 

Terminals 

Tinned copper alloy 

Soldering 

preheating 

soldering 

(referring IEC 61760-1 wave soldering) 

120°C (248°F) / ≤ 120 s 

260 ±5°C (500 ±9°F) / ≤ 10 s 

Cleaning 

max. solvent temp. 

max. immersion time 

 

80°C (176°F) 

30 seconds 

Dimensions 

length (max.) 

width (max.) 

height (max.) 

 

23.0 mm  (0.906”) 

23.0 mm  (0.906”) 

20.0 mm  (0.787”) 

Weight 

23 grams (approx.) 

Compliance 

RoHS, REACH 

Agency approvals 

TÜV: R 50576118 

Electrical insulation system 

Class B 

Packing unit in pcs 

60 per plastic tray / 420 per carton box 

GENERAL DATA 

ORDERING DATA 

XZM-CT50A01 



 

Option 

 nil:  

standard version 

 (xxx):  special version  

WIRING DIAGRAM 

Burden resistor R

L

 and meter not included and shown for reference only. 

Dots indicate winding directions. 

2

1

3

5

PRIMARY

SECONDARY

V

R

L

Reviews: