Written by:.JBJ
Checked by: AC
Document Number: Premier MX Inst Rev: 2
Page 35 of 44
14/12/06
Table 1 - Motherboard Delay Switch Settings
Delay
Duration
S/W 2/2 S/W 2/3 S/W 2/4 S/W 2/5
Delay
disabled
Off Off Off Off
1
min
On Off Off Off
2
min
Off On Off Off
3
min
On On Off Off
4
min
Off Off On Off
5
min
On Off On Off
6
min
Off On On Off
7
min
On On On Off
8
min
Off Off Off On
9
min
On Off Off On
10
min
Off On Off On
10
min
On On Off On
10
min
Off Off On On
10
min
On Off On On
10
min
Off On On On
10
min
On On On On
•
SW 2/6 - Enable Zonal Alarms:
Select the type of sounder alarm response to a fire condition in conjunction
with the Pulse Non Alarm Zones switch described below. [Not EN54
compliant function. Provided to meet existing customer requirements] :
o
OFF: General Alarm Mode – all sounders operate continuously until
silenced.
o
ON: Zonal Sounder Mode - Sounder groups for zones not in the alarm
condition may be selected, via the Pulse Non Alarm Zones switch [SW
2/7], to pulse or not to operate.
Note: Zonal alarms on the 2/4 zone panel affects the standard sounder
circuits on the motherboard. On the 8, 16 and 43 zone panels, it affects
only the [future] expansion module sounder circuits.
•
SW 2/7- Pulse Non Alarm Zones:
Select the type of zonal sounder alarm response to a fire condition in
conjunction with the Zone Alarms switch [SW 2/6] described above. [Not
EN54 compliant function. Provided to meet existing customer
requirements]:
With the Zone Alarms switch [SW 2/6] in the On position [Zonal Sounder
Mode]:
o
SW2/7 OFF: Zonal sounders for zone in the fire condition operate
continuously until silenced. All others are silent.
o
SW2/7 ON: Zonal sounders operate continuously - all other sounders
operate in pulsed mode until silenced.