background image

Written by:.JBJ 

Checked by: AC 

Document Number: Premier MX Inst Rev: 2 

 Page 33 of 44 

14/12/06 

 

To clear the invalid condition, select the config switch to OFF. Reset the 
fire alarm condition before attempting the configuration process again. 

15.6 

List of configuration DIL switches and their functions 

 

SW 1/1 - Inhibit F/P on NLZ

:  

Selects Fire Protection relay to operate 

or

 not to operate for a fire 

condition on any zone configured to non-latched mode.  

o

 

OFF Fire Protection relay operates for a fire condition on any zone 
configured to non-latched mode.  

o

 

ON: Fire Protection relay does not operate for a fire condition on any 
zone configured to non-latched mode.  

o

 

[Not EN54 compliant function]. 

 

 

S/W 1/2 - Delay Alarm Sil & Rst:  

o

 

OFF: Silence and reset available as normal. 

o

 

ON: Prevents alarms being silenced or reset for a period of 3 minutes 
after a fire alarm condition occurs. 

o

 

[Not EN54 compliant function]. 

 

 

SW 1/3 – Delay On Auto:  

o

 

OFF: Automatically turn off the delay mode once a day at the set time 
[the delay mode first being turned on manually]. 

o

 

ON: Automatically turn the delay mode on once a day and off once a 
day at the set times. 

o

 

Requires optional clock module. 

 

 

SW 1/4 - Config Non-Latch Zones:  

o

 

OFF: Configuration mode disabled. 

o

 

ON: Enables selected zones to be configured to non-latching fire mode 
via the Engineer’s Select feature.  

o

 

[Not EN54 compliant function]. 

 

 

SW 1/5 - Config I/S Zones:  

o

 

OFF: Configuration mode disabled. 

o

 

ON: Enables selected zones to be configured to Intrinsically Safe alarm 
thresholds and passive end of line fault monitoring via the Engineer’s 
Select feature. [For use with appropriate I.S. barriers/Isolators, 
typically 330 Ohm zener barriers or galvanic isolators].  

o

 

Not EN54 compliant function. Provided to meet existing customer 
requirements. 

 

 

SW 1/6 - Config M/S Zones:  

o

 

OFF: Configuration mode disabled. 

o

 

ON: Enables selected zones to be configured to short circuit fire mode 
via the Engineer’s Select feature. 

 

 

SW 1/7 - Config Delay Zones:  

o

 

OFF: Configuration mode disabled. 

Summary of Contents for Premier MX-16

Page 1: ...res 12 10 Premier MX C1632 16 zone expansion board Features 13 11 Power Supplies 13 11 1 Visual indications 13 11 2 Battery Disconnect 14 11 3 32 zone Premier MX Power Supply Features And Connections...

Page 2: ...tputs 31 15 4 Engineer s Zone Output Configuration Time out Warning 32 15 5 Invalid Configuration conditions 32 15 6 List of configuration DIL switches and their functions 33 15 7 Configurable Options...

Page 3: ...anel General Assembly with optional clock timer module 9 Figure 7 Typical Wiring Diagram 10 Figure 8 C1627 field termination 11 Figure 9 C1632 16 zone expansion board field termination 11 Figure 10 C1...

Page 4: ...nstallation The following supporting documentation is also available Premier MX Sales Literature Premier MX Panel Application Guide Premier MX User Manual Wiring Recommendations 5 Overview of Installa...

Page 5: ...UTPUTS 1 2 3 4 1 TB4 TB5 TB6 2 3 4 BATT THERM L5 L4 L2 L3 J18A FID2 J18A C FAULT ROUTING ALARM CIRCUITS TB12 TB14 1 2 TB17 TB15 TB16 O P TB18 24V 3 4 SIL AUX D C 0V INPUTS EVAC RST J8 J12 J16 FIRE PRO...

Page 6: ...T TB11 T HERM TB13 C FAULT ROUTING ALARM CIRCUITS 14 15 TB9 TB10 16 TB12 TB14 8 6 7 1 2 TB17 TB15 TB16 O P TB18 24V 3 4 SIL AUX D C 0V INPUTS EVAC RST J 8 J 12 J16 I O EXPA NSION J 20 TB23 ZONE E XPA...

Page 7: ...1 TB4 TB5 12 13 TB7 TB6 2 3 4 5 BATT TB11 THERM TB13 C FAULT ROUTING ALARM CIRCUITS 14 15 TB9 TB10 16 TB12 TB14 8 6 7 1 2 TB17 TB15 TB16 O P TB18 24V 3 4 SIL AUX D C 0V INPUTS EVAC RST J8 J12 J16 I O...

Page 8: ...ocument Number Premier MX Inst Rev 2 Page 8 of 44 14 12 06 Figure 4 2 4 Zone Premier MX panel General Assembly with optional clock timer module Figure 5 8 16 Zone Premier MX panel General Assembly wit...

Page 9: ...Written by JBJ Checked by AC Document Number Premier MX Inst Rev 2 Page 9 of 44 14 12 06 Figure 6 32 Zone Premier MX panel General Assembly with optional clock timer module...

Page 10: ...o Aux DC 24 V 24 V DC relay Typical zonal output wiring Field relay spec Coil resistance 2 6 to 4 5 k Ohms Voltage 24 V DC Nom min 18 V max 30 V Fitted with suppression diode as shown Relay local to f...

Page 11: ...4 Precept 2 4 8 16 32 Zone Circuits 13 14 15 16 9 10 11 12 Grey fill indicates I O available on selected panel Alarm Circuits 1 2 3 4 Aux DC 24V 0V SIL Inputs Outputs Repeater EVAC RST DIS EVAC A B S...

Page 12: ...ply LED indicators OUTPUT OK Battery Charger Fault Charger Fault Mains Fault J18 Earth Fault Monitoring Link Secondary AC from transformer C1631 Repeater Interface Connector for C1632 Zone Expansion B...

Page 13: ...voltage is adjustable from 25V to 28 2V via a small trimmer potentiometer on the PCB As the output voltage is factory set however this should not be necessary 11 1 Visual indications The following vi...

Page 14: ...1 The supply provides a battery disconnect facility which disconnects the batteries when the battery terminal voltage falls below 19 5V 11 3 32 zone Premier MX Power Supply Features And Connections F...

Page 15: ...nts on the display board and the control board due to electrostatic discharge You should discharge any static electricity you may have accumulated by touching a convenient earthed object such as an un...

Page 16: ...ttery swelling Batteries are irrecoverable from this condition and should be replaced LOW TEMPERATURE will prolong battery life but reduce output capacity DANGER Do not incinerate batteries If placed...

Page 17: ...6 off 1 Engineer s door keys Key Ref 801 Flat key type Key Ref 801 Flat key type 1 Access Control keys Key Ref 801 Tubular key type Key Ref 801 Tubular key type 1 Positive battery lead Red Red 1 Negat...

Page 18: ...o the two remaining mounting points Fix the enclosure to the wall using all three mounting points 13 Carefully remove the required knock outs in the panel enclosure and gland all field wiring in place...

Page 19: ...The location of the motherboard battery terminals are shown in Figure 10 C1627 Premier MX motherboard layout and Figure 12 32 zone Premier MX power supply layout Fit the connector on the end of the b...

Page 20: ...following equipment should be available where possible to minimise commissioning time i VHF UHF Portable Radio for two engineers ii Multi meter or equivalent 13 2 Commissioning Checklist 1 Before com...

Page 21: ...ith no field wiring connected configuring the panel in accordance with the site specific requirements and carrying out a functional check iii Functional testing of all circuits and field devices to ch...

Page 22: ...spare end of line devices supplied and leave the EOL devices in the panel terminals at this stage Remember to remove any links fitted to detector bases Be very careful to maintain correct polarity at...

Page 23: ...ted in the standard default mode without any additional configuration The basic default mode is All zones latching fire non delay standard non intrinsically safe Fire Routing Fire Protection and Sound...

Page 24: ...correctly in line with the panel configuration The Fire Routing and Fire protection outputs operate correctly in line with the panel configuration o Press the Silence Alarms and the Reset buttons aft...

Page 25: ...Commissioning the Fire and Fault Routing Outputs 1 Remove the resistor from the Fire Routing output circuit terminals and connect the field wiring to the terminals observing correct polarity Check tha...

Page 26: ...ld be verified in turn by initiating a fire condition on each of the appropriate zones disabling enabling a zone operating the Evacuate button on the panel s display 13 7 8 Commissioning repeaters 1 P...

Page 27: ...irst repeater address to 0 Check that the panel indicates a Repeater fault and any additional repeaters display a steady Comms fault LED 12 Set the first repeater address back to normal and check that...

Page 28: ...ult Routing Output is disabled 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 0 1 C E L No 1800456 32 ZONE FIRE POWER SUPPLY ON POWER SUPPLY FAULT SYSTEM FAULT...

Page 29: ...nce before reset is configured alarms silence switch has been operated 1 Press to stop the buzzer sounding in fire or fault conditions When controls are locked or unlocked Silence Buzzer 2 In 2 Stage...

Page 30: ...d locate the appropriate DIL switch on the motherboard Config Non latch Zones Config I S Zones Config Delay Zones Config Delay O Ps and move the switch actuator to the ON position The CONFIG ENABLED L...

Page 31: ...re normal operation The fault disabled LED will clear By repeating steps 2 and 3 any number of zones or outputs can be configured 4 To quit the programmable configuration mode o To return the panel to...

Page 32: ...ut Configuration condition 1 minute after the last button press o The panel buzzer will restart o The Select LED will flash o The System Fault LED will continue flashing Press the Select On Off button...

Page 33: ...tion SW 1 3 Delay On Auto o OFF Automatically turn off the delay mode once a day at the set time the delay mode first being turned on manually o ON Automatically turn the delay mode on once a day and...

Page 34: ...ounders to operate only when the panel is in the evacuate condition o Not EN54 complaint function Provided to meet existing customer requirements SW 2 1 Silence Before Reset Select type of reset mode...

Page 35: ...General Alarm Mode all sounders operate continuously until silenced o ON Zonal Sounder Mode Sounder groups for zones not in the alarm condition may be selected via the Pulse Non Alarm Zones switch SW...

Page 36: ...uantity set SW1 on the C1631 fitted to the fire alarm panel in line with Table 2 C1631 setting for quantity of repeaters Table 2 C1631 setting for quantity of repeaters SW 1 Repeater Quantity 0 1 2 3...

Page 37: ...ck Module configuration and setting 16 1 Standard Module Engineer Mode 16 1 1 To zero the alarm counter Open panel door and move the DIL switch 1 pole 2 on clock module PCB to the ON position Return t...

Page 38: ...or DISABLE to change MM to desired value 00 to 59 Press SELECT Time Set Display HH MM SS SS flashing Time Set Press ENABLE or DISABLE to reset the SS value to zero To set Day Night Mode On Time Press...

Page 39: ...00 to 59 Press SELECT to exit back to Delay On Off Set Display D N ON or D N OFF Change Change Pressing SELECT repeats the cursor display changes as above Pressing SELECT repeats the cursor display ch...

Page 40: ...enabled 1 Left Off No effect Fitted 1 Right On No effect Removed 2 Left Off Day Night Mode and Fire Event Counter mode enabled Removed 2 Right On Day Night Mode enabled Fire Event Counter mode disabl...

Page 41: ...or Message WP DIL switch operated when timer is not in Timer Set Mode Normal Time Display flashes with WP DIL switch message HH MM SS or HH MM SS D N ON D N OFF Changes to pulses every second WP DILSW...

Page 42: ...te Both EEPROMs can be erased by the following procedure 1 Power the panel down 2 Place the WP DIL switch in the ON position 3 Power the panel back up 4 Return the WP DIL switch to the OFF position wh...

Page 43: ...arning Replace only with identical type rating of BEAB or VDE approved fuse T1A H250V 1A anti surge T3 15A H250V 3 15A anti surge T3 15A H250V 3 15A anti surge T3 15A H250V 3 15A anti surge T1A H250V...

Page 44: ...tery size For one 12 V pack 134mm x 67mm x 60mm 151mm x 65mm x 94mm 151mm x 98mm x 94mm 180mm x 76 mm x 167mm 134mm x 67mm x 60mm 134mm x 67mm x 60mm 134mm x 67mm x 60mm Battery circuit protection War...

Reviews: