User Indications
This section gives an overview of the functions available to the end user.
14.1
User Indications
General Indicator Section
Indicator Description
Indication
Colour
Operating Condition
Power Supply On
Green
Illuminates Steady for Mains or Standby power On.
Fire
Red
Flashes on any new fire alarm condition, changing to a steady indication on
operation of Silence Alarms.
Fire Routing Active
Red
Illuminates Steady when the Fire Routing Output is active.
General Fault
Yellow
Flashes for any fault condition.
Power Supply Fault
Yellow
Flashes for mains or standby power supply/charge fault
System Fault
Yellow
Illuminates Steady to indicate Microcontroller or Memory Failure.
Flashes to indicate Engineer’s Configuration Mode active.
Earth Fault
Yellow
Flashes for any positive or negative power supply earth fault.
Fuse Fault
Yellow
Flashes for any auxiliary supply fuse failure
Repeater Fault
Yellow
Flashes for any Repeater fault or repeater communication fault,
Sounder Fault/Disabled
Yellow
Flashes for any sounder fault. Steady for sounders disabled.
Sounder Test
Yellow
Illuminates Steady while sounder walk test is active.
Fire Protection Fault/Disabled
Yellow
Flashes for a fault on the Fire Protection Output. Steady when Fire
Protection Output is disabled.
Fire Routing Fault/Disabled
Yellow
Flashes for a fault on the Fire Routing Output. Steady when Fire Routing
Output is disabled.
Fault Routing Fault/Disabled
Yellow
Flashes for a fault on the Fault Routing Output. Steady when Fault Routing
Output is disabled.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
0
1
C.E.L. No 1800456 - 32 ZONE
FIRE
POWER SUPPLY ON
POWER SUPPLY FAULT
SYSTEM FAULT
GENERAL FAULT
EARTH FAULT
FUSE FAILED
REPEATER FAULT
FAULT ROUTING FAULT/DISABLED
SOUNDER FAULT/DISABLED
SOUNDER TEST
FIRE PROTECTION FAULT/DISABLED
FIRE ROUTING ACTIVE
FIRE ROUTING FAULT/DISABLED
BUZZER
SILENCE
EVACUATE
RESET
ENABLE
DISABLE
TEST
TEST DISPLAY
ALARMS
RESOUND
SELECT
ON/OFF
SELECT
SILENCE/
OVERRIDE
ON/OFF/
DELAY
ZONE LOCATION
ZONE LOCATION
FIRE
1. THE RED ZONE INDICATOR
WILL PULSE SHOWING THE
LOCATION OF THE FIRE.
2. CARRY OUT THE
REQUIRED FIRE DRILL.
3. TO SILENCE ALARMS
PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE
CONDITION PRESS RESET.
FAULT
1. DETERMINE THE CAUSE
OF THE FAULT.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE
ENGINEER.
SYSTEM FAULT
THE PANEL IS INOPERATIVE.
ARRANGE FOR
ALTERNATIVE FIRE
DETECTION MEASURES.
DISABLEMENT AND TEST
1. PRESS SELECT ON/OFF.
THE LED WILL ILLUMINATE.
2. SELECT THE ZONE OR
OUTPUT USING
↑
AND
↓
. THE
FAULT LED WILL PULSE.
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT
THE ZONE OR OUTPUT AND
PRESS ENABLE.
MODEL:
PRECEPT EN 32
EN54-2: 1997, EN54-4: 1997
C.I.E. PRODUCTION PERIOD: 1
Certificate Number 018c/06
2 1 : 1 8 : 0 5
D / N OF F
Zone Location Indications
Indicator Description
Indication
Colour
Operating Condition
User Generated Zone Location Text
Red
Flashes when zone is in a fire condition, turning to steady on
operation of Silence Alarms.
User Generated Zone Location Text
Yellow
Flashes when zone is in a fault condition. Illuminates steady when
zone is disabled or in test.
Access Controls Keyswitch:
0 – Controls Locked
1 – Controls Unlocked
User Instructions
Clock Module [Optional]:
Showing time and Day/Night off
Back light flashes for Clock
Module fault.