Written by:.JBJ
Checked by: AC
Document Number: Premier MX Inst Rev: 2
Page 17 of 44
14/12/06
12.2
Installation Instructions
1. Carefully remove the control panel from the packing and lie the panel on a flat
surface.
2. Open the door of the panel.
3. Locate the spares bag and check that the following items are present:
Quantit
y
Description Type
Premier MX 2/4
Premier MX 8/16/32
1
Mains Fuse
T1AH250V 20mm
T3.15AH250V 20mm
1
Battery Fuse
F2AL250V 20mm
F5AL250V 20mm
[8/16]
F6.3AL250V 20mm
[32]
* End-Of-Line
capacitors
for
normal zone monitoring
22
μ
F, 35 V axial.
*[2/4 off]
22
μ
F, 35 V axial.
*[8/16/32 off]
*
End-Of-Line resistors for
alarm circuits and zones
configured as Intrinsically
Safe.
3k9 0.25W
*[4/8 off]
3k9 0.25W
*[12/20/36 off]
1
Engineer’s door keys
Key Ref.:
801 [Flat key type]
Key Ref.:
801 [Flat key type]
1
Access Control keys
Key Ref.:
801 [Tubular key
type]
Key Ref.:
801 [Tubular key
type]
1
Positive battery lead
Red
Red
1 Negative
battery
lead Black
Black
1 Battery
coupling
lead Blue
Blue
4
Battery terminal insulation
boot
[32 zone panel only]
N/A
Precept 32 only
12.2.1
Premier MX Panel Installation Instructions
1. Disconnect the display ribbon cable from the motherboard header.
2. Disconnect the earth strap connecting the door and backbox via the spade terminal
on the door.
3. Unscrew the hinge pin at the bottom of the door whilst supporting the door. Swing
the bottom of the door clear of the backbox and pull the door away from the top
hinge pin.
4. Place the door carefully to one side and replace the bottom hinge pin in the
backbox.
5. Unscrew and remove the two lower chassis screws and
only slacken
the top two
mounting screws.