DYCU-3 Dynameco Extinguisher Control Unit
DOC: GLT.MAN-136
1
ISSUE: 1 DATE: 3/9/2009 AUTHOR: NRPJ
DYCU-3 AEROSOL FIRE EXTINGUISHER CONTROL
UNIT
OPERATION MANUAL
Page 1: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 1 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ DYCU 3 AEROSOL FIRE EXTINGUISHER CONTROL UNIT OPERATION MANUAL...
Page 2: ...DYCU 3 Dynameco Extinguisher Control Unit DOC GLT MAN 136 2 ISSUE 1 DATE 3 9 2009 AUTHOR NRPJ INDEX INTRODUCTION 3 CONNECTIONS 4 OPERATION 5 LINKING 6 TECHNICAL INFO 7...
Page 3: ...reaction to stop thus extinguishing the fire These canisters are electrically triggered so need to be connected to a control unit The DYCU 3 is a low cost unit designed to trigger 3 canisters from a...
Page 4: ...Dynameco Canister OUT3 Connection to third Dynameco Canister ALARM 24V output Energises when unit triggered 24V OUT Connection to power external Detector 100mA max CALL Manual Triggering input eg Cal...
Page 5: ...urn off OUTPUT 2 and then turn on OUTPUT 3 to trigger a third canister After another 0 5 second the unit will turn off OUTPUT 3 It will continue with it s internal buzzer operating and its alarm outpu...
Page 6: ...ed together Either 1 2 or all 3 signals can be linked Whatever is more appropriate for type of system being designed Controller 1 Controller 2 In the above example the yellow call point would trigger...
Page 7: ...ondensing IP RATING IP43 SIZE 234 x 165 x 80mm WEIGHT 200g ELECTRICAL MODEL DYCU 3 PART NO 83 005 SUPPLY VOLTAGE 24V DC POWER UP CURRENT 1A STANDBY CURRENT 20mA ACTIVE CURRENT 50mA 1A for Canister Seq...