![Zeta Alarm Systems SMARTCONNECT SMART/REP Installation Manual Download Page 26](http://html1.mh-extra.com/html/zeta-alarm-systems/smartconnect-smart-rep/smartconnect-smart-rep_installation-manual_932115026.webp)
Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
26
SCM-RM Field Wiring Connections
SCM-RM Specifications
Multi Relay Modules (SCM-RM)
Contact Form
3 x Form C
Switching Capacity
5 A, 30VDC (resistive)
5 A, 250VAC (general use)
Circuit Type
Power limited & Not Supervised.
Modes
Common alarm, Common fault, Common tech alarm or Programmable
Recommended cable sizes
18 AWG to 14 AWG (0.8mm
2
to 2.5mm
2
)
NOTE:
When an MRM relay is configured as an alarm output, it will act as a common
alarm relay, and cannot be controlled by cause and effect.