inBOX 24 / inBOX 20
http://www.zennio.com
Technical Support:
http://support.zennio.com
23
122
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
123, 153, 183, 213 2 Byte
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 1
External Sensor Temperature
124, 154, 184, 214 2 Byte
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Temperature Source 2
External Sensor Temperature
125, 155, 185, 215 2 Byte
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Effective Temperature
Effective Control Temperature
126, 156, 186, 216
1 Byte
I
C - - W -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Protection
[Tx] Special Mode
1-byte HVAC Mode
127, 157, 187, 217 1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: comfort
0 = Off; 1 = On
128, 158, 188, 218 1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: standby
0 = Off; 1 = On
129, 159, 189, 219 1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: economy
0 = Off; 1 = On
130, 160, 190, 220 1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Special Mode: protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] Special Mode: protection
0 = Off; 1 = On
131, 161, 191, 221 1 Bit
I
C - - W -
DPT_Window_Door
0/1
[Tx] Window Status (input)
0 = Closed; 1 = Open
132, 162, 192, 222 1 Bit
I
C - - W -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
133, 163, 193, 223
1 Byte
O
C T R - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Protection
[Tx] Special Mode Status
1-byte HVAC Mode
134, 164, 194, 224 2 Byte
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Setpoint
Thermostat Setpoint Input
2 Byte
I
C - - W -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Basic Setpoint
Reference Setpoint
135, 165, 195, 225 1 Bit
I
C - - W -
DPT_Step
0/1
[Tx] Setpoint Step
0 = -0.5ºC; 1 = +0.5ºC
136, 166, 196, 226 2 Byte
I
C - - W -
DPT_Value_Tempd
-670760.00 -
670760.00
[Tx] Setpoint Offset
Float Offset Value
137, 167, 197, 227 2 Byte
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Setpoint Status
Current Setpoint
138, 168, 198, 228 2 Byte
O
C T R - -
DPT_Value_Temp
-273.00 - 670760.00
[Tx] Basic Setpoint Status
Current Basic Setpoint
139, 169, 199, 229 2 Byte
O
C T R - -
DPT_Value_Tempd
-670760.00 -
670760.00
[Tx] Setpoint Offset Status
Current Setpoint Offset
140, 170, 200, 230 1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Offset Reset
Reset offset
141, 171, 201, 231 1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[Tx] Mode
0 = Cool; 1 = Heat
142, 172, 202, 232 1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[Tx] Mode Status
0 = Cool; 1 = Heat
143, 173, 203, 233 1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] On/Off
0 = Off; 1 = On
144, 174, 204, 234 1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] On/Off Status
0 = Off; 1 = On
145, 175, 205, 235 1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] Control Variable (Cool)
PI Control (Continuous)