Z70 v2
88
( 0 )
Minimum
Medium
Maximum
Here, the Auto mode is only activated by long press.
Allow speed 0
: sets whether the speed level 0 will be present or not. When the
Auto
Mode without a dedicated object
has been configured, this option will be necessarily
activated.
2.2.2.1.4.4
Special Mode
Boxes configured as special mode controls include two buttons that let the user sequentially
commute between the different special climate modes, as well as an icon indicator that will adopt
an aspect or another depending on the currently active special mode.
Figure 83
Climate Control - Special Mode
When this function is assigned to the box, two 1-byte objects (
“
[Ci] (Climate) Special Mode
Control
” as the control object, and “
[Ci] Special Mode Indicator
” as the status object) will be
enabled. The former will be sending the bus the value that corresponds to the mode that the
user selects by touching the buttons (see Table 8.
Special Modes vs. Icon vs. Object Value
), while the status object (which can receive values from the bus although it gets self-updated
as well on button presses) will determine the indicative icon represented in the box at any time.
If this object receives an unrecognised value from the bus, no icon will be displayed in the
indicator.