QUAD Plus
Technical Support:
5
2
CONFIGURATION
2.1
GENERAL
After importing the corresponding database in ETS and adding the device into the
topology of the desired project, the configuration process begins by right-clicking into
the device and selecting
Edit parameters
.
ETS PARAMETERISATION
The only parameterisable screen available by default is General. From this screen it is
possible to activate/deactivate all the required functionality.
Figure 2
General.
Heartbeat (Periodical Alive Notification)
: enables the “
[Heartbeat] Object
to Send ‘1’
” one-bit object, which will be sent with a value of “1” and a
configurable period to notify that the device is still working (still alive).
Input x
: sets the type of input number “x”: “Binary Input”, “Temperature
Probe” or “Motion Detector”. If such input is not required, it can be left as
“Disabled”.
Thermostat x
: enables or disables thermostat number “x”.
One entry per input or thermostat will be included into the tab tree on the left.