Depending on the type of output, binary or analogue, the reactions to the button
presses will differ.
Binary output
: short or long-pressing the button will commute the on-off
state of the relay.
0-10V analogue output
: the behaviour is the same as described for the Test
Off Mode, except that the fan status objects do not change (they will be
updated when leaving the Test On Mode).
Disabled output
: under the Test On mode, disabled outputs will behave as if
they were enabled, thus, as described above (depending on whether they are
binary or analogue outputs).
The lock, timer, alarm and scene functions will not work while the device is under the
Test On mode, but will be taken into account when leaving the Test On Mode. Status
objects will not be sent to the bus, either.
Important
:
the device is factory delivered with both manual modes (Test Off and Test
On) enabled
.
ETS PARAMETERISATION
The
Manual Control
is configured from a specific tab which can be enabled from the
General screen (see section 2.1).
Figure 14
Manual Control.
The only two parameters are:
Manual Control
: options
are “Disabled”, “Only with Test Off Mode”, “Only
with Test On Mode
” and “Test Off Mode + Test On Mode” (default).
Depending on the selection, the device will permit using the manual control
under the Test Off, the Test On, or either of the two modes. Note that, as