MAXinBOX 16 Plus. Multi-Function Actuator 16 outputs 16A
ZIO-MB16P
Technical Documentation
FEATURES
8 different channels:
o
Shutter channels (up to 8).
o
Individual outputs (up to 16).
o
2-pipes Fan Coil control (up to 4 units).
Manual output operation with push button and
LED status indicator.
Suitable for capacitive loads, maximum
140 µF
.
Logical functions included.
Output timing facilities.
Total data saving on power failure.
Size 90 x 60 x 140 mm (8 DIN units).
DIN rail unit assembly (EN 50022), with snap fit
clamp.
No external power supply required other than the
bus.
KNX BCU integrated.
Possibility to connect different phases in adjoining
outputs.
CE directives compliant.
6
1
4
5
7
3
2
Figure 1. MAXinBOX 16 Plus
1
. Upper outputs
2
. Lower
outputs
3
.Programming/Test
LED
4
.KNX
connector
5
.Programming/Test
button
6
.Output control
button
7
.Output status LED
indicator
Programming/test button
: short button press to set
programming mode. If this button is held while plugging the
device into the KNX bus, it goes into safe mode. If this button is
held more than 3 seconds, the device goes into manual mode
(test mode).
LED:
programming mode indicator (red). When the device
goes into safe mode, it blinks (red) every half second. It lights
in green when the device is in manual mode. During start up
(after reset or power failure), if the device is not in safe mode,
programming LED blinks in blue for a few seconds.
GENERAL SYSTEM SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX
supply
Voltage (typical)
29VDC SELV
Voltage range
21
…31V DC
Maximum
consumption
Voltage
mA
mW
29VDC (typical)
11
320
24VDC
12.5
300
Starting
25
725
Bus connection
Typical bus connector TP1, 0.50 mm² section
External power supply
No
Ambient temperature
0ºC to +55ºC
Storage temperature
-20ºC to +70ºC
Ambient humidity
5 to 95% RH (no condensation)
Storage humidity (relative)
5 to 95% RH (no condensation)
Complementary characteristics
Class B
Safety class
II
Operation type
Continuous operation
Device action type
Type 1
Electrical solicitations period
Long
Type of protection
IP20, clean environment
Assembly
Independent control assembly device to be mounted inside of electrical panels
with DIN rail (EN 50022).
Power failure response
Data saving and relay status change according to parameterization.
Response when restarting
Data recovering and output status change according to parameterization
Operation indication
Programming LED indicates programming mode (red) and test mode (green).
Output status LED indicators reflect current output state.
Weight
525
gr.
PCB CTI index
175 V
Enclosure
PC FR V0 halogen free