Zennio KLIC-TS User Manual Download Page 1

   

 

 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

KLIC-TS 

 

 

 

 

 

KNX 

 AB Gateway for  

Toshiba AC Units 

 

 

 

 

 

 

 

 

U

S

E

R

 M

A

N

U

A

L

 

 

 

 

ZCL-TS 

 

 

 

Application program version: [1.0]  

User manual edition: [1.0]_a 

 

 

 

www.zennio.com

  

 

 

Summary of Contents for KLIC-TS

Page 1: ...KLIC TS KNX AB Gateway for Toshiba AC Units USER MANUAL ZCL TS Application program version 1 0 User manual edition 1 0 _a www zennio com...

Page 2: ...nstallation 4 1 3 Start Up and Power Loss 5 2 Configuration 6 2 1 General 6 2 2 Inputs 8 2 2 1 Binary Input 8 2 2 2 Temperature Probe 8 2 2 3 Motion Detector 9 2 3 Logic Functions 10 2 4 A C Gateway 1...

Page 3: ...it can be monitored and periodically sent to the KNX bus to inform other devices The most outstanding features of KLIC TS are Bidirectional control of Toshiba A C units through the connection wires AB...

Page 4: ...into the programming mode making the associated LED 1 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode The LED will blink in red...

Page 5: ...on security and installation procedures please refer to the device Datasheet bundled in the device packaging and also available at http www zennio com 1 3 START UP AND POWER LOSS Depending on the conf...

Page 6: ...interfacing with the A C unit and to the management of the climate control system ETS PARAMETERISATION After importing the corresponding database in ETS and adding the device into the topology of the...

Page 7: ...pectively AC Temperature Setpoint and AC Temperature Setpoint Status allow setting the desired temperature setpoint or reading the current value respectively See section 2 4 1 for further options AC R...

Page 8: ...ll not work properly with KLIC TS ETS PARAMETERISATION When Inputs has been activated in the General parameters screen the following drop down lists will be available for the selection of the specific...

Page 9: ...ZN1IO DETEC P motion detector is compatible with a variety of Zennio devices However depending on the device it is actually being connected to the functionality may differ slightly Therefore please re...

Page 10: ...ution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after execu...

Page 11: ...y function depending on the A C unit Moreover KLIC TS allows configuring several advanced functions Setpoint limits to restrict the range for the temperature setpoint External reference temperature wh...

Page 12: ...t state When KLIC TS is notified about a change it updates the status objects and sends them to the KNX bus In addition KLIC TS provides an error management function see section 2 4 4 which allows sen...

Page 13: ...ue A C unit mode 0 Auto 1 Heating 3 Cooling 9 Fan only 14 Dry Table 1 A C unit operating modes Additionally a simplified mode can be configured to select Cooling and Heating mode Simplified Mode in ad...

Page 14: ...Percentage Control and its related status object AC Flaps Percentage Control Status The total number of positions is five Control Values Status Value Position Sent to the Unit 1 20 20 Position 1 21 40...

Page 15: ...hether it is currently active respectively When this function is deactivated flaps will go to position 5 in heating mode and to position 1 in the rest of the modes Moreover the polarity of this parame...

Page 16: ...r Automatic Speed 1 Bit objects AA Speed Automatic and AA Speed Automatic Status activate automatic speed and informs the currently state respectively Moreover the polarity of this parameter can be se...

Page 17: ...n the configured limits it will actually send the limit value Minimum Cooling Auto Dry Mode sets the upper limit Maximum Heating Auto Mode sets the lower limit Once these limits are enabled several ob...

Page 18: ...values provided by an external temperature probe and these values will be employed by the A C unit to control the temperature instead of employing its internal values If during 3 minutes no temperatu...

Page 19: ...ilable parameters in ETS are Seconds enables the 2 Byte object AC Operating time s This object can be read and overwritten during executing time Hours enables the 4 Byte object AC Operating time h Thi...

Page 20: ...switch off state KLIC TS will still monitor any control orders being received setpoint fan speed etc so they can be applied once it leaves such state Automatic Off Object Polarity sets the polarity o...

Page 21: ...e reception of scene trigger values through the KNX bus See section 2 4 3 2 4 2 INITIAL CONFIGURATION The custom initial configuration allows setting the desired status that KLIC TS will send the A C...

Page 22: ...s If enabled the status objects will be sent to the KNX bus after applying the parametrized delay Note even if this option is not enabled the status objects may be sent to the KNX bus if the initial c...

Page 23: ...efined next On Off No Change the state the machine had before the power failure On or Off Mode No Change Heating Cooling Fan Dry or Automatic Note if fan mode is selected setpoint temperature and auto...

Page 24: ...rors reported by the A C unit itself KLIC TS can notify the KNX bus about the reported error code although referring to the specific documentation of the A C unit is advisable in order to obtain furth...

Page 25: ...rror in A C unit AC AC Unit Error Error Code 14 Byte object which provides error code In case the A C unit reports an error the former object will send a value of 1 while the latter will report the co...

Page 26: ...0 1 Ix Probe Error 0 No Alarm 1 Alarm 14 20 26 1 Bit I C W DPT_Enable 0 1 Ix Input Lock 0 Unlock 1 Lock 15 21 27 1 Bit C T DPT_Switch 0 1 Ix Short Press 0 Sending of 0 1 Bit C T DPT_Switch 0 1 Ix Sho...

Page 27: ...ontrol 0 63 128 191 Ix Short Press Run Scene Sending of 0 63 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Short Press Save Scene Sending of 128 191 1 Bit I O C T R W DPT_Switch 0 1 Ix Switch Sensor Edg...

Page 28: ..._Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0x9 Inc by 100 0xF Inc by 1 Ix Long Press Brighter Long Pr Brighter Release Stop 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by...

Page 29: ...0 Bottom 32 1 Byte I C W DPT_SceneControl 0 63 128 191 Motion Detector Scene Input Scene Value 33 1 Byte C T DPT_SceneControl 0 63 128 191 Motion Detector Scene Output Scene Value 34 63 92 1 Byte O C...

Page 30: ...147 148 149 150 151 152 1 Bit I C W DPT_Bool 0 1 LF 1 Bit Data Entry x Binary Data Entry 0 1 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 1 Byte I C W DPT_Value_1_Ucount 0 255 LF 1...

Page 31: ...ive Error AC Unit Error 213 14 Bytes O C T R DPT_String_ASCII AC AC Unit Error Error Code See AC Unit Manual 214 1 Byte I C W DPT_Scaling 0 100 AC Speed Percentage Control 0 Automatic 0 4 33 3 S1 33 8...

Page 32: ...DPT_Switch 0 1 AC Automatic Off Status 0 Activated 1 Deactivated 228 2 Bytes I C W DPT_TimePeriodSec 0 3600 AC Automatic Off Delay 0 3600 s 0 Disabled 229 2 Bytes O C T R DPT_Value_Temp 273 00 670760...

Page 33: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...