ANNEX II. COMMUNICATION OBJECTS INBOX 24 VT
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
I/O
Flags
Data type (DPT)
Functional Range
Name
Function
1
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending of 0
2
1 Bit
C - - T -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending of 1
3
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Lock; 1 = Unlock
1 Bit
I
C - W - -
DPT_Enable
0/1
Lock Manual Control
0 = Unlock; 1 = Lock
4
1 Bit
C - - T -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
5
1 Byte
I
C - W - -
DPT_SceneControl
0-63; 128-191
[Thermostat] Scene Input
Scene Value
6
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Temperature Source 1
External Sensor Temperature
7
2 Bytes
I
C - W - -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Temperature Source 2
External Sensor Temperature
8
2 Bytes
O
C R - T -
DPT_Value_Temp
-273.00º - 670433.28º
[Tx] Effective Temperature
Effective Control Temperature
9
1 Byte
I
C - W - -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Tx] Special Mode
1-Byte HVAC Mode
10
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Comfort
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Comfort
0 = Off; 1 = On
11
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Standby
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Standby
0 = Off; 1 = On
12
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Economy
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Economy
0 = Off; 1 = On
13
1 Bit
I
C - W - -
DPT_Ack
0/1
[Tx] Special Mode: Protection
0 = Nothing; 1 = Trigger
1 Bit
I
C - W - -
DPT_Switch
0/1
[Tx] Special Mode: Protection
0 = Off; 1 = On
14
1 Bit
I
C - W - -
DPT_Window_Door
0/1
[Tx] Window Status (Input)
0 = Closed; 1 = Open
15
1 Bit
I
C - W - -
DPT_Trigger
0/1
[Tx] Comfort Prolongation
0 = Nothing; 1 = Timed Comfort
16
1 Byte
O
C R - T -
DPT_HVACMode
1=Comfort
2=Standby
3=Economy
4=Building
Protection
[Tx] Special Mode Status
1-Byte HVAC Mode