background image

 

 

 

inBOX 24 v2 / inBOX 20 v2

 

http://www.zennio.com

 

              

Technical Support:

 

http://support.zennio.com

 

 

16 

2.6

 

MASTER LIGHT (ONLY inBOX 24 v2) 

The  Master  Light  function  brings  the  option  to  monitor  the  state  of  up  to  12  light 

sources 

–or any other functionally-similar element whose state is transmitted through a 

binary  object

– and, depending on those states, perform a 

master  order

  every  time  a 

certain trigger signal (again, a binary value) is received through a specific object.  

Such master order will consist in: 

  A 

general switch-off

 order, if at least one of the up to twelve status objects is 

found to be on. 

  A 

courtesy  switch-on

  order,  if  none  of  the  up  to  twelve  status  objects  is 

found to be on. 

Note that the above switch-off and switch-on orders are not necessarily a binary value 

being sent to the bus 

– it is up to the integrator the decision of what to send to the KNX 

bus  in  both  cases:  a  shutter  order,  a  thermostat  setpoint  or  mode  switch  order,  a 

constant  value,  a  scene…  Only  the  trigger  object  and  the  twelve  status  objects  are 

required to be binary (on/off). 

The  most  typical  scenario  for  this  Master  Light  control  would  be  a  hotel  room  with  a 

master  pushbutton  next  to  the  door.  When  leaving  the  room,  the  guest  will  have  the 

possibility  of  pressing  on  the  master  pushbutton  and  make  all  the  lamps  turn  off 

together.  Afterwards,  back  on  the  room  and  with  all  the  lamps  off,  pressing  on  the 

same master pushbutton will only make a particular lamp turn on (e.g., the closest lamp 

to the door) 

– this is the courtesy switch-on. 

ETS PARAMETERISATION 

Once the Master Light function has been enabled, a specific tab will be included in the 

menu on the left. This new parameter screen contains the following options: 

 

Number  of  State  Objects

:  defines  the  number  of  one-bit  status  objects 

required. The  minimum (and default)  value  is  “1”,  and  the maximum  is “12”. 

These objects are called “

[ML] Status Object n

”. 

Summary of Contents for inBOX 20 v2

Page 1: ...inBOX 24 v2 inBOX 20 v2 Multifunction Actuator for Flush Mounting ZIOIB24V2 USER MANUAL ZIOIB20V2 ds kmfroi Application program version 1 1 1 2 User manual edition 1 2 _a www zennio com...

Page 2: ...ation 4 1 3 Start Up and Power Loss 5 2 Configuration 6 2 1 General 6 2 2 Inputs Only inBOX 24 v2 8 2 2 1 Binary Input 8 2 2 2 Temperature Probe 9 2 2 3 Motion Detector 9 2 3 Outputs 10 2 3 1 Manual C...

Page 3: ...dividual ON OFF outputs 4 multi purpose inputs only in inBOX 24 v2 configurable as Temperature probe either models provided by Zennio or other NTC temperature probes from other suppliers being in that...

Page 4: ...entirely analogous for inBOX 20 v2 although the inputs are not available The main elements of the device are described next Test Prog Pushbutton 3 a short press on this button sets the device into the...

Page 5: ...evice and also available at www zennio com 1 3 START UP AND POWER LOSS During the start up of the device the Test Prog LED will blink in blue colour for a few seconds before the device is ready Extern...

Page 6: ...TION From the General screen it is possible to activate deactivate all the required functionality Figure 2 Default screen Once activated Inputs only on inBOX 24 v2 Outputs Logic Functions Thermostats...

Page 7: ...eat Periodical Alive Notification this parameter lets the integrator incorporate a one bit object to the project Heartbeat Object to Send 1 that will be sent periodically with value 1 to notify that t...

Page 8: ...detector from Zennio Important older models of the Zennio motion detector e g ZN1IO DETEC and ZN1IO DETEC N will not work properly with inBOX 24 v2 ETS PARAMETERISATION When Inputs has been activated...

Page 9: ...product section at the Zennio website www zennio com 2 2 3 MOTION DETECTOR It is possible to connect motion detectors from Zennio to the input ports of inBOX 24 v2 Please refer to the specific user ma...

Page 10: ...therefore available per output Manual operation can be done in two different ways named as Test On Mode for testing purposes during the configuration of the device and Test Off Mode for a normal use a...

Page 11: ...d the device will act over the output according to the length of the button press and to the current state A long press makes the shutter start moving upwards or downwards depending on the button bein...

Page 12: ...eaving the Test On mode the status objects will recover the values they had prior to entering Test On As the device is never aware of the actual position of the shutter as the shutter drive does not p...

Page 13: ...g pressing the Prog Test button Lock Manual Control unless the above parameter has been Disabled the Lock Manual Control parameter provides an optional procedure for locking the manual control in runt...

Page 14: ...xecution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterizable communication objects The result after ex...

Page 15: ...4 v2 implements four Zennio thermostats which can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the inBOX 24 v2 product section at the...

Page 16: ...at to send to the KNX bus in both cases a shutter order a thermostat setpoint or mode switch order a constant value a scene Only the trigger object and the twelve status objects are required to be bin...

Page 17: ...off takes off Scene if checked object ML General Switch off Scene will be enabled which will send a scene run save order configurable in Action and Scene Number whenever the general switch off takes o...

Page 18: ...http support zennio com 18 when the courtesy switch on takes place in contrast to object ML General Switch Off Binary Object which sends the value 0 during the general switch off as explained above F...

Page 19: ...ending for that output or that channel such temporisation will be interrupted and only the delay and the action of the new scene will be executed ETS PARAMETERISATION Prior to setting the scene tempor...

Page 20: ...the scene temporisation Therefore parameter Scene m Z Delay defines the delay that will be applied to the action defined in Z for the execution of scene m where Z may be a specific individual output...

Page 21: ...Byte I C W DPT_SceneControl 0 63 128 191 Thermostat Scene Input Scene Value 6 44 82 120 2 Bytes I C W DPT_Value_Temp 273 00 670760 00 Tx Temperature Source 1 External Sensor Temperature 7 45 83 121 2...

Page 22: ...t 0 1 Tx Setpoint Reset Reset Setpoint to Default 1 Bit I C W DPT_Reset 0 1 Tx Offset Reset Reset Offset 24 62 100 138 1 Bit I C W DPT_Heat_Cool 0 1 Tx Mode 0 Cool 1 Heat 25 63 101 139 1 Bit O C T R D...

Page 23: ...eneControl 0 63 128 191 ML General Switch Off Scene Scene Sending 175 1 Byte C T DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection ML General Switch Off HVAC mode Auto Comfort Standby E...

Page 24: ...0 0xF Inc by 1 Ix Short Press Brighter Increase Brightness 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0xD Inc by 100 0xF Inc by 1 Ix Short Press Darker Decrease Bright...

Page 25: ..._UpDown 0 1 Ix Long Press Move Up Shutter Sending of 0 Up 1 Bit C T DPT_UpDown 0 1 Ix Long Press Move Down Shutter Sending of 1 Down 1 Bit C T DPT_UpDown 0 1 Ix Long Press Move Up Down Shutter Switchi...

Page 26: ...Ix Long Press Release Stop Shutter Release Stop Shutter 209 215 221 227 1 Byte I C W DPT_Scaling 0 100 Ix Long Press Dimming Status Input 0 100 1 Byte I C W DPT_Scaling 0 100 Ix Long Press Shutter Sta...

Page 27: ...T_Switch 0 1 Ix Cx Detection State Binary Binary Value 259 264 269 288 293 298 317 322 327 346 351 356 1 Bit I C W DPT_Enable 0 1 Ix Cx Enable Channel According to parameters 260 265 270 289 294 299 3...

Page 28: ...1 On 496 1 Bit I C W DPT_UpDown 0 1 CA Auto Move 0 Raise 1 Lower 497 1 Bit I C W DPT_Step 0 1 CA Auto Stop Step 0 Stop StepUp 1 Stop StepDown 1 Bit I C W DPT_Step 0 1 CA Auto Stop 0 Stop 1 Stop 498 1...

Page 29: ...Data Entry 665 666 667 668 669 670 671 672 4 Bytes I C W DPT_Value_4_Count 2147483648 2147483647 LF 4 Byte Data Entry x 4 Byte Data Entry 673 674 675 676 677 678 679 680 681 682 1 Bit O C T R DPT_Bool...

Page 30: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Reviews: