Futher information
Page 1/2
HeatingBOX 230V 4X
Heating actuator for up to 4 outputs 230VAC
ZCL-4HT230
TECHNICAL DOCUMENTATION
FEATURES
•
4 configurable outputs for 230VAC valve control.
•
4 thermostats.
•
10 logic functions.
•
Total data saving on KNX bus failure.
•
Manual control through buttons and status LED indicators.
•
Common 230VAC supply required for the 4 outputs.
•
Integrated KNX BCU.
•
Dimensions 67 x 90 x 35mm (2 DIN units).
•
DIN rail mounting (EN 50022), through pressure.
•
Conformity with the CE directives (CE-mark on the right side).
1. 230V input (live phase)
2. Valve outputs
3. Output control button
4. Output status Indicator LED
5. Programming/Test LED
6. Programming/Test button
7. KNX connector
3
2
7
5
4
6
1
Figure 1: HeatingBOX 230V 4X
Programming/test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe
mode. If this button is held for more than 3 seconds, the device enters the test mode.
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.
GENERAL SPECIFICATIONS
CONCEPT
DESCRIPTION
Type of device
Electric operation control device
KNX supply
Voltage (typical)
29VDC SELV
Voltage range
21..31VDC
Maximum
consumption
Voltage
mA
mW
29VDC (typical)
7.5
217.5
24VDC¹
10
240
Connection type
Typical TP1 bus connector for 0.80mm Ø rigid cable
External power supply
230V 50/60Hz (only phase, for valve supply)
Operation temperature
0°C .. +55°C
Storage temperature
-20°C .. +55°C
Operation humidity
5 .. 95% (No condens.)
Storage humidity
5 .. 95% (No condens.)
Complementary characteristics
Class B
Protection class
II
Operation type
Continuous operation
Device action type
Type 1
Electrical stress period
Long
Degree of protection
IP20, clean environment
Installation
Independent device to be mounted inside electrical panels with DIN rail (EN
50022)
Minimum clearances
Not required
Response on KNX bus failure
Data saving according to parameterization
Response on KNX bus restart
Data recovery according to parameterization
Operation indicator
The programming LED indicates programming mode (red) and test mode
(green). Each output LED indicates its status (fixed=active output;
flashing=overload or short-circuit). The blue blinking of the programming
LED indicates a 3 minutes lock due to the suffering of 3 short-circuits in less
than 3 minutes.
Weight
98g
PCB CTI index
175V
Housing material
PC FR V0 halogen free
¹ Maximum consumption in the worst case scenario (KNX Fan-In model)