background image

© Zennio Avance y Tecnología S.L. 

Edition 5 

Futher information 

www.zennio.com

 

Page 1/2 

 

FANinBOX 230V 1CH 

3-speed ceiling fan controler @230VAC 

ZCLFB230C1 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

External 230V 50/60Hz power supply 

 

Up to 3 speeds control for ceiling fans 

 

Manual control through push button and LED indicator 

 

10 logic functions 

 

Total data saving on KNX bus failure 

 

Integrated KNX BCU 

 

Dimensions 67 x 90 x 35mm (2 DIN units) 

 

DIN rail mounting (EN 50022), through pressure 

 

Conformity with the CE directives (CE-mark on the right side) 

 

 

 

1. Power supply input 

2. Fan output 

3. Speed control buttons 

4. Speed indicator LEDs 

5. Programming/Test button 

6.  Programming/Test LED 

7. KNX Connector 

Figure 1: FANinBOX 230V 1CH 

Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe 
mode. If this button is held for more than 3 seconds, the device enters the test mode. 
 
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual mode 
is indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it  starts a blue blinking sequence. 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29VDC SELV 

Voltage range 

21..31VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29VDC (typical) 

3.9 

113.1 

24VDC¹ 

10 

240 

Connection type 

Typical TP1 bus connector  for 0.80mm Ø rigid cable 

External power supply 

230VAC 50/60Hz 

Operation temperature 

0°C .. +55°C 

Storage temperature 

-20°C .. +55°C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class / Overvoltage category 

II / III (4000V) 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection / Pollution degree 

IP20 / 2 (clean environment) 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (EN 
50022) 

Minimum clearances 

Not required 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The  programming LED indicates programming mode (red) and test mode 
(green).  The  output  LEDs  indicate its  status  (fixed  =  full  speed;  fast/slow 
flashing = high/slow speed; off = stoped) 

Weight 

109g 

PCB CTI index 

175V 

Housing material / Ball pressure test temperature 

PC FR V0 halogen free / 75ºC (housing) - 125ºC (connectors) 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 

Reviews: