Zennio DALI BOX Broadcast 4CH v2 Manual Download Page 1

© Zennio Avance y Tecnología S.L. 

Edition 1 

Further information 

www.zennio.com

 

Page 1/2 

 

DALI BOX Broadcast 4CH v2 

KNX - DALI Broadcast Interface for up to 4 channels 

ZDIDLB4V2 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

Control of 4 channels with up to 64 DALI ballasts per channel 

 

Single Master DALI-2 Controller 

 

Compatibility with color ballasts (DT8) 

 

Supports KNX Data Secure 

 

Ballast replacement allowed with automatic detection 

 

Error detection and monitoring (except multiaddress DALI ballasts) 

 

Burn-in, Stand-by and Auto-off functionality for each channel 

 

Optional manual dimming control 

 

External 110-240 VAC 50/60 Hz power supply 

 

Total data saving on KNX bus failure 

 

Integrated KNX BCU (TP1-256) 

 

Dimensions 67 x 90 x 79 mm (4.5 DIN units) 

 

DIN rail mounting according to IEC 60715 TH35, with fixing clamp 

 

DALI Standard certified according to IEC 62386 

 

Conformity with the CE, UKCA, RCM directives (marks on the right 
side) 

 

 

 

Figure 1: DALI BOX Broadcast 4CH v2 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29 VDC SELV 

Voltage range 

21-31 VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29 VDC (typical) 

3.3 

95.7 

24 VDC¹ 

10 

240 

Connection type 

Typical TP1 bus connector for 0.8 mm Ø rigid cable 

External power 
supply 

Voltage 

110-240 VAC 50/60 Hz PF=0.5 

Maximum consumption 

175 mA @ 110 VAC / 100 mA @ 230 VAC 

Operation temperature 

-5 .. +45 °C 

Storage temperature 

-20 .. +55 °C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class / Overvoltage category 

II / III (4200 V) 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (IEC 
60715) 

Minimum clearances 

Not required 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The programming LED indicates programming mode (red) and test mode 
(green). Each output LED indicates its status (fixed = active output; flashing 
= error in the output). Power supply LED indicates the presence of supply 
voltage (green). 

Weight 

221 g 

PCB CTI index 

175 V 

Housing material 

PC FR V0 halogen free 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 

Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe 
mode. If this button is held for more than 3 seconds, the device enters the test mode. In order to perform a KNX Secure factory reset, while the device is 
in safe mode, press the button for 10 seconds until the programming LED changes its state. 
 
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The test mode is 
indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash.

 

 

1. DALI channel status LED

 

2. DALI channel control button

 

3. Programming/Test LED

 

4. Programming/Test button

 

5. DALI channel output

 

6. External supply LED

 

7. External power supply

 

8. KNX connector

 

 