28
Start-up configuration
: this function is meant to define the behaviour of the shutter
channel outputs after a bus power failure or after programming the device with ETS. A default
or custom configuration can be selected.
When a default configuration is chosen, after a partial or complete download from ETS,
ACTinBOX MAX6 interprets that the shutter is completely up (0%), independently of its real
status. For the blinds with slats, ACTinBOX MAX6 asummes that they are completely opened
(0%), no matter their real status.
After a bus power failure, the position of the shutter will be the one it had before the bus failure
(and so the slats).
When a custom configuration is chosen, ETS will show the following window:
Figure 3.17. Custom Start-up configuration
Where to configure the following parameters:
Initial position:
this field defines the exact initial position for the shutter should be
located after a bus power failure or after programming the device. The following statuses
can be chosen: Current position (keeps stopped), up, down, or specific position (locate
the shutter in the position established in the parameter "Select Shutter Position [%]",
shown when choosing this option).
Update:
by enabling this field (“Yes”), the shutter position can be sent to the bus, by
means of the corresponding communication object, to feedback the rest of the devices in
the installation when needed. Besides, it can be defined a sending delay. If a value 0 is
set, the status is sent immediately.
Note: The initial status is always sent through the object “[CX] Current Shutter position”
(and "[CX] Current Slats position", for blinds with slats).