For blinds with slats it also appears the 1 byte object "[CX] Slats Positioning", through which
establishing the desired position (in percentage) for the slats.
Scenes:
this function makes possible to use scenes for controlling the shutters. It allows
choosing a precise position where to locate the shutter depending on the scene number
received by ACTinBOX MAX6 through the 1 byte object “Scenes (Shutter Channels)”.
Besides running scenes, it is possible to
learn
(modify) scenes, taking into account that the
associated numerical values to learn scenes are in the range 128-191 (the values 0-63 are
reserved for running scenes).
Up to 5 scenes
can be run and/or learnt, for each shutter channel.
Figure 3.13. Scenes
The “Scene” parameter indicates the number of the scene at which the shutter will react. If this
value is 0, the corresponding scene is disabled.
“Response” indicates the precise position where to locate the shutter when the corresponding
scene number is called from the bus. The shutter can be positioned up, down, or in a specific
position of its length (in percentage, from 0% to 100%). In case of choosing this last option,
the parameter "Shutter specific position?" is enabled, where to set a specific position for the