Besides the type of the shutters, the user must configure their specific functions, common to both
types of shutters:
Times:
to define the different times (in tenths of seconds) associated to the shutter
movement, such as:
Main time (Shutter length):
this is the time the shutter needs to cover its length
completely. Both times (rising time or lowering time) can be used in this field, but if there
was some difference between these two times, Lowering time will be considered as
“master” and should be used to fill in this field. Rising time in this case will be set in the
“Total Time Up” field, enabled for this purpose (when selecting “Yes” in the field “Are total
Time Up and Down different?”).
This variable will not need to be periodically calibrated, since the exact shutter position
remains on ACTinBOX MAX6 (even when the power failure occurs).
Security time (pause to change the movement direction):
this time is applied by
the actuator to protect the drive when the movement direction of the shutter is changed. If
the device receives the order to lower the shutter while this is being raised, ACTinBOX
MAX6 will stop it for a while (security time) to later lower it. It is recommended to keep the
default value in this field: 5 tenths of second.
Are total time Up and Down different?:
whenever the shutter rising and lowering
times are different (e.g. heavy shutters) this field should be dropped down to set the rising
shutter time, as mentioned before. The lowering time must be set in the “Main time” field.
Additional time when the shutter gets the limit:
this parameter guarantees the
shutter always gets its lowest or highest level, level by setting an extra time for the drive
to keep moving once the shutter took up its rising/lowering times, preventing small
maladjustments. This parameter appears disabled by default, but it is recommended to
set a value on it, to ensure the proper movement of the shutter.
If the shutter is the type Blind with slats (see figure 3.12), some other times and specific
parameters appear. All of them are explained in detail in the Annex I of this manual.
Note: After programming the device with ETS, ACTinBOX MAX6 considers the shutter is
completely raised, so any raising order will be ignored.
Below an example of a possible shutter configuration.