ZENN
iO
AVANCE Y TECNOLOGÍA
vwww.zennio.com
14
Figure 3.7. Scenes
There is a 1-byte communication object associated with Scenes for the individual outputs:
"Scenes (Individual Outputs)", which shows when the "Outputs" box in ETS is enabled, even if
the outputs are disabled.
In the case of individual outputs, the scenes allow linking a numerical value (between 1 and
64, where 0 means that the scene is disabled) to an output status (OFF or ON). Thus, when
the predefined numerical value for a scene is received through the Scenes object, the
parameterized action for the output will be carried out: OFF or ON; so it will be possible to
create different environments in the installation.
Besides running scenes, it is possible to
learn
(modify) scenes, taking into account that the
associated numerical values to learn scenes are in the range 128-191.
ACTinBOX MAX6 allows running and/or learning
up to 5 different scenes
for each output.
Alarm
: it can be configured one alarm for each output. Once activated, this alarm will
have
priority
over the rest of orders that the actuator receives, i.e., any order received while
the alarm is activated will be ignored until the alarm deactivation.