Zencontrol zc-blind Manual Download Page 1

Dimensions

Mounting options

Independently mounted control for surface mounting

Mounting centres

470 / 150 mm

Dimensions

197 / 500 / 57 mm

Product range

Order code

Description

zc-blind

Full feature blind controller

Installation

Remove the product from the box and inspect it for any damage. If you 

believe the product to be damaged or otherwise unsound, 

do not

 install 

the product. Please pack it back into its box and return it to the place of 

purchase for replacement. 

If the product is satisfactory, proceed with the installation: 

Ensure safety warnings are adhered to

.

Mount the unit as shown in 

fig 1 

or 

fig 2 

using the appropriate 

fasteners (not included).

Wire terminal I/O and secure using provided cable clamps or M20 

cable glands as per the wiring diagram in 

fig 3.

Connect starter leads to output channels 

per wiring diagram in 

fig 4-6.

1

Safety information

 

This product must only be installed by a licensed electrician.

 

Before commencing installation or servicing turn off and isolate all 

supply circuits.

 

Risk of accidental contact with live parts. Do not energise with product 

open or disassembled.

 

There are no user serviceable parts, attempting to service any part of the 

product will void the warranty

 

DALI is not SELV and as such should be treated as LV.

 

As the installer, it is your responsibility to ensure you comply to all 

relevant building and safety codes. Refer to application standards for the 

relevant rules.

 

When the installation is complete, leave this manual with the building’s 

owner for future reference.

 

Each circuit must be protected by a MCB rated at 16 A or less

Blind controller  

zc-blind

Surface mount

2

Rod mount

Up to 15 mm 

threaded rod

M6 fastener

x4

x4

Specifications

Supply voltage

230 V ~ 50 Hz

DALI supply current

235 mA

Output rating

Maximum 250 mA

Guaranteed supply 235 mA

Terminal capacity

Mains 1 - 4 mm

2

Digital I/0  0.5 - 2.5 mm

2

Lighting circuits

3

Load per circuit

10 A

Motor channels

4

Load per channel

375 W /  

1

/

2

 HP

1.6 A inductive load

Operating temperature

0 to 45°C

Material

PC

Classification

Class I

197

500

57

57

470

150

170 mm

= 3 - 5 core

Recommended cable clearance

200 mm

= 6 core