47/50
User Manual for HYD 3-6 kw ES Hybrid Inverter - Rev. 1.1 del 13/06/2019
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
ID54
SciCommLose
SCI Communication is
faulty
and then switch it back on again. Check if the
problem has been resolved.
If not, contact ZCS Technical Support.
ID55
RecoverRelayFail
Relay fault.
ID56
PvIsoFault
Insulation resistance is
too low.
Check the insulation resistance between the
photovoltaic string and the ground. If there is
any dispersion towards the ground, resolve the
problem.
ID57
OverTempFault_BAT
Battery temperature is
too high
Make sure that the HYD-ES inverter is installed
away from direct sunlight.
Make sure that the HYD-ES inverter is installed
in a cool, well-ventilated place.
Make sure that the inverter is installed
vertically and that the ambient temperature is
below the limits tolerated by the HYD-ES
inverter.
ID58
OverTempFault_
HeatSink
Heatsink temperature is
too high.
ID59
OverTempFault_Env
Ambient temperature is
too high.
ID60
PE connectFault
Check the grounding of the AC output of the PE
cable
ID65
UnrecoverHwAcOCP
Grid current is too high
and has caused an
unrecoverable
hardware failure.
ID65- ID67 are internal faults of the HYS-ES
inverter; switch off the inverter, wait 5 minutes
and then switch it back on again. Check if the
problem has been resolved.
If not, contact ZCS Technical Support.
ID66
unrecoverBusOVP
Bus voltage is too high
and has caused an
unrecoverable fault.
ID67
BitEPSunrecover
BatOCP
Unrecoverable battery
overcurrent fault in EPS
mode
ID68
UnrecoverIpv
Unbalance
Input current is not
balanced and has
caused an
unrecoverable fault.
Check the settings of the HYD-ES inverter’s
photovoltaic input mode (parallel/independent
mode). If this is not correct, change the
photovoltaic input mode.
ID70
unrecoverOCPInstant
Grid current is too high
and has caused an
unrecoverable fault.
ID70- ID73 are internal faults of the HYS-ES
inverter; switch off the inverter, wait 5 minutes
and then switch it back on again. Check if the
problem has been resolved.
If not, contact ZCS Technical Support.
ID73
UnrecoverIPVInstant
Input current is too high
and has caused an
unrecoverable fault.
ID74
UnrecoverPvConfigSetWrong
Incorrect input mode
Check the HYD-ES inverter’s photovoltaic input
mode (parallel/independent mode). If this is
not correct, change the photovoltaic input
mode.
ID75
unrecoverEEPROM_W
Unrecoverable EEPROM
writing
ID75-ID77 are internal faults of the HYS-ES
inverter; switch off the inverter, wait 5 minutes