Fault Indicator System ENQ4 

L05 

 

E61-283-00 

Operating Instructions

 

English translation 

Errors and technical changes reserved 

 

Simplify maintenance 

 

Report faults 

 

Avoid damages 

 

Reduce service costs 

 

The  ENQ4  offers  a  complete  fault  indicator  unit  for  recording 

unapproved  operating  conditions  such  as  excessive  pressure 

or  excessive  temperature  in  a  compact  design.  The  devices  are 

successfully used with compressors, automatic production machi-

nes, vehicles, heating systems and air-conditioners. 

The  closing  of  the  input  S5  activates  the  opening  of  the 

contact  A1-14  without  storage  function.  The  contact  will 

close  with  the  opening  of  S5  provided  that  an  input  S1-S4 

do not have a fault report.  
 
Additionally  each  input  is  equipped  with  a  signal  delay  of 

about  200  ms  for  the  purpose  of  filtering  out  any  possible 

current  interruptions  occurring  momentarily.  Therefore  the 

switching  on  of  the  connected  machine  by  A1-14  and  the 

simultanous closing of the contacts S1..S4 do not lead to a 

fault report. 
These  measures  permit  the  use  of  the  equipment  with  un-

shielded input cables up to 100 m in length. 

 

Safety 

Precautions 

against electrostatic discharge (ESD protection). 

 

Opening the device, any manipulation of the device and 

the avoidance of the safety facilities are not permitted. 

 

All relevant safety regulations and standards must be 

attended to. 

 

Non-observance of the safety regulations may cause 

death, severe injuries or substantial damage to property. 

 

Before use, please, read the operating instructions and 

keep it in a safe place. Make sure that the operating 

instructions are always available for installation, initial 

operation and maintenance.  

 

The installation and operation must be carried out by 

qualified personnel only,  

 

who is familiar with the professional handling of machine 

equipment, 

 

who is familiar with the valid rules of  industrial safety 

and accident prevention,  

 

who read and understood the operating instructions and 

the system manual.  

 

The safe function of the device during machine operation 

cannot be guaranteed in case of wrong connection or 

improper operation. This may lead to fatal injuries.  

 

Pay attention to country specific regulations. 

 

The electrical installation must be performed after dis-

connecting the device and the machine from the mains 

supply. 

 

The  wiring must be carried out according to the instruc-

tions of this operating manual. 

 

The person who programs the device must be protected 

Non-observance  of  the  instructions  above  will  cause  the 

loss of warranty.

 

Correct Use 

Features

 

Function

 

During normal operation (all external contacts on the inputs 

S1..S4 are closed) the internal contact A1-14 is closed.  
The  alarm  contact  A1-14  (NC)  opens  as  soon  as  a  fault 

alarm input S1..S4 opens. The machine is switched off until 

the fault is acknowledged.  
Each  input  channel  has  a  storage  function  so  that  faults 

occurring  even  sporadically  are  recognised.  The  acknow-

ledgment  takes  place  with  the  interruption  of  the  power 

supply of the ENQ4 system. 
There  are  4  fault-detection-inputs  and  one  additionel  test 

input,  which  operates  directly  to  the  output  contact  of  the 

unit. 
Each fault (input signal-contact open) will be indicated by a 

red LED at the front panel, the fault free operation is shown 

by  a  green  LED.  The  report  is  made  through  NC-contacts 

so that separate cable monitoring is assured. 
Various  operating/reporting  voltages  up  to  AC  230V  are 

available. 
 

Special function test operation (input S5): 

Installation

 

ENQ4 is a panel-mounting device for 45

 

x

 

45

 

mm cutout.  

It has a plastic front panel IP54 with identification panel for 

the  fault  messages.  A  paperstrip  for  inscriptions  is  en-

closed  at  each  item.  This  strip  can  easily  be  pushed  into 

the considered side pocket. 
In  addition  to  each  fault  report  display,  space  for  text  for 

customer specific formatting of the reports is provided. We 

will supply the devices with the appropriate text as per your 

text documentation for mass production requirements. 
All  electronic  components  are  integrated  in  a  panel-moun-

ting  housing  48

 

x

 

48

 

mm.  The  front  of  the  device  is  water 

and  dust  proof.  Several  modules  can  be  arranged  next  to 

one another in the form of a tableau.  
A plastic front frame with external dimensions of

 

55

 

x

 

55

 

mm 

is available as an accessory.  