ENERGY METER LEM-30

THREE-PHASE DIGITAL 

 

MANUAL INSTRUCTION

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

plik: inst_ext_eng_lem-30 | modyfikacja: 03.07.2017

FETAURES

TECHNCAL DATA

DESCRIPTION

APPEARANCE

LEM-30

Power supply terminals: L1 (IN 1, OUT 5); L2 (IN 2, OUT 6); L3 (IN 3, OUT 7); 

N (IN 4, OUT 8)

Reference voltage: 3 x 230 V / 400 V AC

Voltage tolerance: -15 ÷ +10 %

Nominal frequency: 50 / 60 Hz

Basic current / maximum current: 3 x 10 A / 100 A

Meter power consumption: 10 VA / 2 W 

Measurement accuracy (IEC61036): class 1

LCD display: Counter 5+2 digits

Impulse counting signal: LED red

Impulse output: SO+ SO-: OC type

Impulse output voltage SO+ SO-: 12 ÷ 27 V DC

Impulse output current SO+ SO-: < 27 mA

Constant SO+ SO-: 1000 imp/kWh

Impulse duration SO+ SO-: 90 ms

Number of terminal clamps: 10

Section of connecting cables: main connection: 4 ÷ 25 mm

2

impulse output: minimum 0,2 mm

2

Operating temperature: -25 ÷ +55 

o

C

Casing mounting: TH35 rail (according to EN 60715)

Protection degree: IP51

Protection level: II

Overvoltage category: II

Pollution degree:  2

Dimensions: 72 x 100 x 66 mm

Waga: 0,700 kg

Reference standards: IEC 62053-21; EN50470-1/3

●  maximum current 100A,  

measuring and display of kWh,

●  LCD (display),
●  additional impulse output,
●  four-modular casing,
●  TH 35 rail mounting.

LEM-30 energy meter with a backlit 

display, is used to monitor the three-

phase electricity consumption in com-

mercial and industrial applications. 

 

It measures and displays the kWh. It is 

possible to connect a measuring device, 

due to an additional impulse output. The 

meter can be mounted in distribution 

boards or can be connected to an exter-

nal power supply source.

The device is designed 

for three-phase installa-

tion and must be installed 

in accordance with stand-

ards valid in a particu-

lar country. The device 

should be connected 

according to the details included in this 

operating manual. Installation, connec-

tion and control should be carried out by 

a  qualified  electrician  staff,  who  act  in 

accordance with the service manual and 

the device functions.

Disassembling of the device is equal 

with a loss of guarantee and can cause 

electric shock. Before installation make 

sure the connection cables are not under 

voltage. The cruciform head screwdriver  

4 mm should be used to install the device. 

Improper transport, storage, and use of 

the  device  influence  its  wrong  function-

ing. It is not advisable to install the device 

in the following cases: if any device part 

is missing or the device is damaged or 

deformed. In case of improper function-

ing of the device contact the producer.

CAUTION!

The symbol means selective 

collecting of electrical and 

electronical equipment. It 

is forbidden to put the used 

equipment together with other 

waste.

Output terminals

L1 (5), L2 (6),  

L3 (7), N (8)

Impulse output

Impulse  

counting signal

Input terminals

L1 (1), L2 (2),  

L3 (3), N (4)

LCD display