TECHNICAL DATA

CECHy

DESCRIPTION

ی  Wersje o napięciach wyjściowych 12 

V i 24 V,

ی  maksymalny prąd wyjściowy 2000 

mA (przy 12 V) oraz 1000 mA (przy 
24 V),

ی  odporność na stan jałowy,
ی  obudowa trzymodułowa,
ی  montaż na szynie TH 35.

Switching  regulators  are  designed  for 
supplying  electronic  (electric)  devices 
with DC voltage.  They are small, light if 
compared to voltage transformer regula

-

tors of the same output power and have 
very good load regulation. 12 V and 24 V 
DC output voltage versions in triple-mod

-

ule casings are available.

ZIM - 12/25

Current range: 0 ÷ 2000 mA

Rated current: 2000 mA

Rated power:

24 W

Output voltage:

12 V DC

Output ripple and  noise voltage(max): 100 mVpp

ZIM - 24/12

Current range: 0 ÷ 1000 mA

Rated current: 1000 mA

Rated power:

24 W

Output voltage:

24 V DC

Output ripple and  noise voltage(max): 140 mVpp

ZIM regulators common parameters

Voltage tolerance: 3 %

Input regulation: 1 %
Load regulation: 1 %

Transient response, rise time: 100 ms, 30 ms

Sustain time: 100 ms

Voltage range: 190 ÷ 260 V~

Frequency range: 50/60 Hz

Efficiency: 82 %

Input curren: 0,3 A

Starting current: Cold start 30 A

Protection classi:

II

Overvoltage category:

II

Pollution level:

2

Operating temperature: -20 ÷ +85 

o

C

Humidity: 10 ÷ 95 %

Rated ambient temperature: +40 

o

C

Breakdown voltage: 3 kV AC

Insulation resistance:: 100 MΩ / 500 V DC

EMI - conducted and radiated: According to PN-EN 55022

Current harmonic: According to PN-EN 61000-3-2-3

Dimensions: triple-module 90x53x66 mm

Weight: 170 g

Standard conformity: PN-EN 60950:2002,

PN-EN 61000-4-2,3,4,5,6,11

NOTE: Minimum distance to the other devices - 10 mm 

Przy braku wymuszonego chłodzenia moc pobierana powinna być zredukowana do  

80% mocy znamionowej!

The  device  should  be 
connected  to  a  single-
phase system according 
to current standards.
The  device  connections 
will  be  described  in  this 

manual.  Only  qualified  electricians  are 
allowed  to  mount,  connect  and  adjust 
the device. It is necessary to read this 
manual  and  know  the  unit  functions 
before the device mounting. Do not di

-

sassembly the device casing or you will 
lose  any  warranty  rights  and  expose 
yourself  to  the  electric  shock  hazard. 
Before  mounting  operation  make  sure 
of  disconnecting  the  connection  wires  
from the electric network.  Use a cross-
head screwdriver of 3.5 mm diameter to 
mount the device. The relay should be 
carried,  stored  and  used  in  an  appro

-

priate way. Do not mount the device in 
case of any device parts lack, damage 
or  deformation.  In  case  of  malfunction 
please notify the manufacturer.

CAUTION

Reviews: