background image

ZCM-42 TIME PROGRAMMER

Wi-Fi-CONFIGURABLE 

USER’S MANUAL

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

tel. +48 32 210 46 65, fax +48 32 210 80 04

www.zamel.com

, e-mail: [email protected]

zcm-42_inst_ext_gb | 09.02.21

APPEARANCE

FEATURES

DESCRIPTION

•  control based on sunrise and sunset times,

•  option to change calculated sunrise and sun-

set times manually,

•  control based on hour and day of the week,

• option to program one-time events and ex-

ceptions,

•  setting parameters via a website thanks to the 

Wi-Fi module,

•  no need to install any applications,

•  settings are kept without requiring a battery.

The ZCM-42 time programmer is used to per-

form time functions in automation and control 

systems. It can control loads connected to out-

puts depending on the hour and day of the week 

as well as sunrise and sunset times (including 

information on geographical coordinates of the 

place of time programmer installation, current 

date, and time shift set). The programmer also 

offers the possibility of setting one-time events 

– executed on a given day of the year – and 

makes it possible to define exceptions (time pe-

riods during which control is executed different-

ly than set in weekly and astro schedules). The 

programmer allows you to program 80 events 

for all types (weekly, astro, and one-time events 

as well as exceptions), but the main advantage 

of this programmer is that they are not simply 

ON/OFF pairs but independent events, which 

allows for very flexible control of the connected 

devices – for example, you can turn on a device 

using the astro function and turn it off using the 

weekly function. Parameters are set via a web-

site thanks to the Wi-Fi module included with 

the device. In addition, the programmer keeps 

device settings without requiring a battery when 

there is a power failure and offers the possibility 

of importing/exporting saved schedules.

Hereby, ZAMEL Sp. z o. o. declares that the 

radio equipment type ZCM-42 is in compliance 

with Directive 2014/53/EU. The full text of the 

EU declaration of conformity is available at the 

following internet address: www.zamel.com

The device should be connected to a one-

phase network in accordance with legally 

binding standards. The connection method 

is described in this manual. Any activities 

related to installation, connection, and ad-

justment  should  be  performed  by  qualified 

electricians who have read this user’s man-

ual and familiarised themselves with device 

functions. Removing the enclosure voids the 

warranty and poses a risk of electric shock. Before installation, 

make sure that there is no voltage on connection cables. To 

install the device, use a cross-head screwdriver with a diam-

eter of 3.5 mm. The proper operation of the device is affected 

by how the device is transported, stored, and used.  It is not 

advisable to install the device in the following cases: lack of 

any components, damage to or deformation of the device. If the 

device operates improperly, please contact the manufacturer.

NOTE

 TECHNICAL DATA

Nominal supply voltage: 230 V AC 50 / 60 Hz

Supply voltage tolerance: -15 ÷ +10 %

Nominal power consumption:

0.75 W - Wi-Fi disabled

0.85 W - Wi-Fi enabled

1.4 W - with one relay turned on

2 W - with two relays turned on

Transmission: Wi-Fi 2.4 GHz b/g/n

Operating range: 100 m in the open area*

Transmitting power: ERP < 20 mW

Supply voltage / Wi-Fi status signalling: LED (green)

Number of outputs: 2

Input state signalling: 2 LEDs (red)

Parameters of relay contacts: 2 x NO/NC 16 A / 250 V AC (inrush: 111 A / 20 ms)

Number of inputs: 2

Can be used with: monostable (returnable), bistable switches

Schedules: astro, weekly, yearly, exceptions

Number of events: 80 for all schedule types

Settings are kept by: supercapacitor - settings are kept for 24 hours

Operating temperature: -10 ÷ +55 °C

Operation position: any

Enclosure mounting: DIN-Rail

Enclosure IP rating: IP20

Number of connection terminals: 10

Cross-section of connection cables  0.2 ÷ 2.5 mm²

Overvoltage category: II

Contamination degree: 2

Dimensions: two-module enclosure 90x35x66 mm

Weight: 163 g

* The operating range given refers to an open area, i.e. ideal conditions, without obstacles. If there are obstacles between the transmitter 

and the receiver, the operating range should be expected to be reduced by: 10-40% for bricks, 5-20% for wood and plaster, 40-80% for 

reinforced concrete, 90-100% for metal, and 10-20% for glass. In addition, overhead and underground high-voltage power lines as well as 

cell towers located near devices have a negative impact on the operating range.

Do not dispose of this device together with 

other waste! To avoid harmful effects on the 

environment and human health, the worn-out 

device should be stored in designated areas. 

Electrical waste from households may be handed 

over to the waste collector established for this 

purpose free of change and in any amount, 

as well as to the store when purchasing new 

equipment.

Output terminals 12, 11, 14

Supply terminals L, N

Input terminals IN1, IN2

Antenna port

Output terminals 24, 21, 22

Power / Wi-Fi activity

signalling

Wi-Fi activation / deactivation

button

Input state signalling

Reviews: